Fan Trays
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
JUNOSg 3.0 G10 CMTS Hardware Guide
162
Fan Trays
To maintain an internal temperature below the maximum operating temperature of the G10
CMTS, all fan trays must be fully functional. If any of the fan trays fails, you must replace it as
soon as possible to ensure the CMTS remains operational.
You can detect a fan tray failure by any of following indicators:
!
A fan tray LED is illuminated red.
!
If enabled, an entry was written the local event log.
!
If enabled, an SNMP message was sent to the NMS indicating a fan failure.
!
The display produced by issuing the
show chassis environment
command shows a fan
speed of 0 RPM.
!
If enabled, an SNMP message was sent to the NMS indicating the temperature of the
CMTS exceeded the temperature high threshold. This might also indicate the ambient
temperature is rising.
Replace a Fan Tray
If a fan tray LED is illuminated red, one or more fans in that tray has failed and you must
replace the fan tray. The fan trays are hot-swappable, which means you can remove and
install them while the system is powered on.
If a fan tray fails to the point where inadequate air ventilation flows through the chassis, the
Chassis Control Module might power down the system if the temperature within the chassis
exceeds the threshold considered safe for system operation.
!
All fans within a fan tray contain top and bottom grills
to provide protection during removal and installation.
Nevertheless, take care when inserting your hand
anywhere in the vicinity of an operating fan.
!
Operating the G10 CMTS without fully functional fan
trays might cause irreparable damage or reduce the
life of one or more modules in the system. After
removing a fan tray, you must immediately install its
replacement.
Содержание G10 CMTS
Страница 8: ... JUNOSg 3 0 G10 CMTS Hardware Guide viii ...
Страница 18: ... JUNOSg 3 0 G10 CMTS Hardware Guide 2 ...
Страница 34: ...G10 CMTS Hardware Overview JUNOSg 3 0 G10 CMTS Hardware Guide 18 ...
Страница 46: ...DOCSIS Module JUNOSg 3 0 G10 CMTS Hardware Guide 30 Figure 12 DOCSIS Module Front Panel HotSwap ...
Страница 55: ... Hardware Component Overview Chassis Control Module 39 Figure 15 Chassis Control Module Front Panel Eth0 ...
Страница 72: ...Chassis Rear Modules JUNOSg 3 0 G10 CMTS Hardware Guide 56 Figure 21 Hard Disk Module Rear Panel C O M Eth ...
Страница 82: ... JUNOSg 3 0 G10 CMTS Hardware Guide 66 ...
Страница 112: ...Rack Mounting JUNOSg 3 0 G10 CMTS Hardware Guide 96 Figure 25 Air Flow Through Chassis ...
Страница 116: ...Rack Mounting JUNOSg 3 0 G10 CMTS Hardware Guide 100 Figure 29 Rack Fully Populated with Three G10 CMTS Chassis ...
Страница 118: ...Install Power Supplies JUNOSg 3 0 G10 CMTS Hardware Guide 102 Figure 30 Power Supply Installation 1 2 ...
Страница 138: ...Connect to Power Sources JUNOSg 3 0 G10 CMTS Hardware Guide 122 Figure 39 DC Power Transition Module ...
Страница 148: ... JUNOSg 3 0 G10 CMTS Hardware Guide 132 ...
Страница 156: ...Upstream RF Measurement JUNOSg 3 0 G10 CMTS Hardware Guide 140 ...
Страница 188: ... JUNOSg 3 0 G10 CMTS Hardware Guide 172 ...
Страница 196: ...Radio Frequency RF Specifications JUNOSg 3 0 G10 CMTS Hardware Guide 180 ...
Страница 202: ...EIA Channel Plans JUNOSg 3 0 G10 CMTS Hardware Guide 186 ...
Страница 203: ... 187 Part 5 Index Index on page 189 ...
Страница 204: ... JUNOSg 3 0 G10 CMTS Hardware Guide 188 ...
Страница 209: ... Index 193 Index V ventilation 69 89 95 101 124 161 162 167 video servers 7 voltage power supply 27 ...
Страница 210: ... Index JUNOSg 3 0 G10 CMTS Hardware Guide 194 ...