Table 15: AC Power Electrical Specifications
(Continued)
Item
Specification
ACX500 Indoor
(ACX500-AC)
ACX500 Outdoor
(ACX500-O-AC)
ACX500 Outdoor with PoE
(ACX500-O-POE-AC)
Maximum AC power
supply output
137 W (80 W PoE)
52 W
128 W (80 W PoE)
NOTE: We recommend that you use a dedicated customer-site circuit breaker rated for
20 A (100 VAC) or 16 A (240 VAC), or as required by local code. Doing so enables you to operate
the router in any configuration without upgrading the power infrastructure.
ACX500 Router AC Power Cord Specifications
Each AC power supply has a single AC appliance inlet that requires a dedicated AC power feed. Most
sites distribute power through a main conduit that leads to frame-mounted power distribution panels,
one of which can be located at the top of the rack that houses the router. An AC power cord connects
each power supply to the power distribution panel.
You can order detachable AC power cords, each approximately 8 ft (2.5 m) long that supply AC power to
the router. The C15 appliance coupler end of the cord, as described by International Electrotechnical
Commission (IEC) standard 60320, inserts into the AC appliance inlet coupler. The plug end of the
power cord fits into the power source receptacle that is standard for your geographic location.
NOTE: For the ACX500 outdoor routers, use the power cord that is purchased from Juniper
Networks, and which is compatible with the ACX500 outdoor routers. Using a power cord other
than that is provided by Juniper Networks with the router can damage the power terminal. The
nominal rating of the DC power source are +24 VDC, –48 VDC, and –60 VDC. These power
cords are specifically designed to be used only with the specified ACX500 outdoor routers.
provides specifications for the AC power cord provided for each country or
region.
70