8 Startup and parameterization
46
8.6.7
Configuring the transistor output DO1 as a pulse output
If the transistor output DO1 is configured as a pulse output, a pulse is generated at this output each time
a selected medium volume is reached.
NOTE!
The units of the displayed values and the values to be entered manually correspond to the values se-
lected in chapter 8.6.2 "Choosing the flow rate unit, the number of decimals, and the counter display
unit", page 38.
Is only displayed if the unit chosen in
the UNIT parameter is in liters or m
3
.
1. Choose the
volume unit
of a pulse.
OUTPUT
DO1
PULSE
LITERS
M3
DO2
PU = 01.000
1. Enter the volume of medium (value be-
tween 0.000 and 9999.9) at which a pulse
is transmitted at the transistor output. If
the unit chosen is in gallons, enter a pulse
in gallons (
see 8.6.2).
2. Deactivating the function: Set PU = 0.
The output is then always open or no
pulse is emitted.
3. Confirm
+