7 Mounting
20
7.2
Installation into the pipeline
The flowmeter is inserted into a fitting (406090) mounted on the pipeline.
7.2.1
Recommendation for installing into the pipeline
Flow velocity requirements
Risk of injury resulting from high pressure levels within the system!
Before working on the system, switch off the pressure and bleed/empty the lines.
Risk of injury resulting from the type of medium!
When using dangerous media, always observe the specifications on the safety sheet and the relevant
accident prevention regulations.
Select the fitting 406090 according to the flow velocity
requirements in the pipeline.
Example A in the diagram:
Requirement: If the flow rate is 10 m3/h, the flow veloc-
ity should ideally be between 2 and 3 m/s.
Solution:
Select a pipe with DN 40.