77
9 Maintenance
Regardless of
the color
20 mA
Depending on the
switching thresh-
olds or switched
The current output
emits a 20 mA sig-
nal, regardless of
the flow rate dis-
played.
•
Check the settings for the current out-
put,
see chapter 8.6.6 "Configuring
Regardless of
the color
22 to 30 mA
Depending on the
switching thresh-
olds or switched
The current output
emits a signal be-
tween
22 and 30 mA.
•
Switch the device's power supply off
and on.
•
If the problem arises again, contact
the manufacturer.
Regardless of
the color
30 mA
Depending on the
switching thresh-
olds or switched
The current output
emits a signal
> 30 mA.
•
Check the current output's connec-
tion.
•
If the problem arises again, contact
the manufacturer.
Regardless of
the color
4 to 20 mA
Depending on the
switching thresh-
olds or switched
The signal value
emitted by the cur-
rent output does not
match the flow rate
measured.
•
Check the settings for the current out-
put,
see chapter 8.6.6 "Configuring
•
Check the OFFSET and SPAN set-
tings for the current output,
see
chapter 8.7.1 "Adjusting the current
output AO1", page 66
Regardless of
the color
4 to 20 mA
The relay outputs DO2 and DO3 do not
switch, regardless of the flow rate dis-
played.
•
Check the settings for the relay out-
puts DO2 and DO3,
see
chapter 8.6.11 "Configuring the relay
outputs DO2 and DO3", page 52
•
Check the flow rate unit
•
Check the outputs' response,
see
chapter 8.7.3 "Checking proper re-
sponse of the outputs", page 70
a
If the output has been configured to switch upon generation of a warning,
see chapter 8.6.5 "Configuring out-
Device sta-
tus LED
Analog out-
put AO1
Digital outputs
DO1/DO2/DO3
Problem
Measure