8 Startup and parameterization
Determining the fitting's K-factor with a Teach-In process in relation to a flow rate (TEACH F.)
1. If you do not wish to change any further parameters, go to the END function in the parameters menu
and press the
key in order to save the settings and return to the process level.
NOTE!
The device starts using the new K-factor as soon as the function SAVE YES is confirmed when leaving
the parameters menu.
1. Charge the pipe.
2. Wait for the flow rate to stabilize.
3. Confirm TEACH F.: MEASURE \ is displayed.
K-FACTOR
K = 10.000
The display shows the K-factor for the fitting (406090)
used, whether entered or determined using Teach-In.
TEACH V.
TEACH F.
MEASURE \
The device calculates the mean flow rate in the pipe
over a period of approximately 50 s.
0.000 L/S
1. Enter the value of the flow rate in the pipe (value
between 0.001 and 9999) and confirm.
The device calculates the fitting's K-
factor and displays it.
K = 2.8500
1. Confirm the displayed value.
OUTPUT
RETURN
VALID N/Y
1. Confirm the K-factor determined through Teach-
In or not.