8 Startup and parameterization
38
8.6.1
Choosing the display language.
The menu is in English when switched on.
1. If you do not wish to change any further parameters, go to the END function in the parameters menu
and press the
key in order to save the settings and return to the process level.
8.6.2
Choosing the flow rate unit, the number of decimals, and the counter display unit
The UNIT function enables you to select the following:
•
Flow rate unit
•
Fixed point (selection 0, 1, 2 or 3) to display the flow rate value in the process level or a sliding point
(selection AUTO): In this case, the device selects the position of the decimal point depending on the
unit selected and the flow rate value measured
•
Counters' volume unit if the flow rate unit selected above is liters or m
3
LANGUAGE
ENGLISH
DEUTSCH
FRANCAIS
1. Confirm the displayed language.
The selected language is immediately ac-
tive.
ITALIANO
ESPANOL
UNIT
NOTE!
Only the counters are automatically converted when the flow rate unit is adjusted.
Convert any other flow rate settings manually if necessary.
NOTE!
The maximum flow value that can be displayed depends on the decimal places selected:
•
9999 if decimal places = 0 or AUTO
•
999.9 if decimal places = 1
•
99.99 if decimal places = 2
•
9.999 if decimal places = 3