12 IO-Link data
64
Switching output 1 and 2
Designation
Index Sub-
index
Data type
Value range
Default Ac-
cess
right
a
a
RW = Read and write access
RO = Read access only
WO = Write access only
Description
output signal
200
and
201
each
switch
ing
output
1
TENUM
TENUM values:
0x00: No value
0x01: Limit value 1
0x02: Limit value 2
0x03: Sensor fault
0x04: Calibration
timer
0x05: Calibration ac-
tive
Switch-
ing out-
put
1:0x01
Switch-
ing out-
put
2:0x02
RW
Inversion
361
2
TENUM
TENUM values:
0x00: No
0x01: Yes
0x00
RW
Output mode
362
3
TENUM
TENUM values:
0x00: p-switching
0x01: n-switching
0x02: push/pull
0x00
RW
Switching opera-
tions limit value
363
4
TUINT32
0 to 99999
0
RW
0 = Limit val-
ue monitor-
ing inactive
Limit value ON
period
363
4
TUINT32
0 to 99999 s
0
RW