-H- Unit configuration
Description
Range
Units
Value
Unit type
0 ‑ 7
-
2 (YLCA)
3 (YLHA)
Number of compressors/circuits
-
4 / 2
Compressor rotation
LIFO
FIFO
PERSONALISED
TIME
-
FIFO
No. of evaporators
1 ‑ 2
-
1
Driver number (EVD400)
0-1-2-4
-
0
Cycle inversion valve logic
NO / NC
-
NC
No. of pumps
1 ‑ 2
-
1 (SINGLE PUMP)
2 (TWO-PUMP ACCESSORY)
Pump rotation
START-UP
TIME
-
TIME
Pump operation
ON WITH COMP. ON
ALWAYS OFF
ALWAYS ON
SAFETY ON/ OFF
ALWAYS ON
No. of hours for pump rotation
0 ‑ 9999
Hours
12
ON/OFF digital input activation
YES/NO
-
NO
WINTER/SUMMER digital input activation
YES/NO
-
NO
ON/OFF activation with Monitor
YES/NO
-
NO
WINTER/SUMMER activation with Supervisor
YES/NO
-
NO
WINTER/SUMMER operation inversion delay
Seconds
10
Monitoring protocol
CAREL
GSM MODEM
ANALOGUE MODEM
RS 232
LONWORKS
MODBUS
-
CAREL
Selection of communication speed
1200
2400
4800
9600
19200
Bauds
19200
Monitoring ID number
0 ‑ 200
-
1
Selection of language at start-up
YES/NO
-
YES
Restore default values (Warning!)
YES/NO
-
NO
User manual
1
General description of the unit
1.1
15