Alarm table

Description

Input

Off circ.1

Off circ.2

Off fan

Off

pump

Off sys

Reset

Delay

Notes

Serious alarm FC, PG

ID1

X

 

 

 

 

MANUAL

-

general Phase

control protec‐

tion

Antifreeze alarm

B6

X

X

X

X

X

MANUAL

-

The pump can be

running in OFF

mode. See Anti‐

freeze menu

Thermal protector

pump 1 Q5

ID4

X

X

X

X

X

MANUAL

-

If it is available,

pump 1 starts up

If not, the entire

system stops.

Thermal protector

pump 2 Q6

ID18

X

X

X

X

X

MANUAL

-

If it is available,

pump 1 starts up

If not, the entire

system stops.

PDW flow switch, FS

ID2

X

X

X

X

X

MANUAL

Selectable

Delays on start-

up and while op‐

erating

Circ. 1 fan heat

switches THPF1,

THPF2

ID9

X

-

Circ. 1

-

-

AUTO/

MANUAL

1st fault within 60'

interval, automatic

reset

2nd fault within

60' interval, man‐

ual reset

Circ. 2 fan heat

switches THPF3,

THPF4

ID14

-

X

Circ. 2

-

-

AUTO/

MANUAL

2nd fault within 60'

interval, automatic

reset

2nd fault within

60' interval, man‐

ual reset

Compressor 1 A1 heat

switches (YCSA/LCA

150, YCSA-H/BRAW

150)

ID7

Comp 1

-

-

-

-

AUTO/

MANUAL

3rd fault within 60'

interval, automatic

reset

3rd fault within

60' interval, man‐

ual reset

Compressor 2 A2 heat

switches (YCSA/LCA

150, YCSA-H/BRAW

150)

ID8

Comp 2

-

-

-

-

AUTO/

MANUAL

4th fault within 60'

interval, automatic

reset

4th fault within

60' interval, man‐

ual reset

Compressor 3 A3 heat

switches (YCSA/LCA

150, YCSA-H/BRAW

150)

ID12

-

Comp 3

-

-

-

AUTO/

MANUAL

5th fault within 60'

interval, automatic

reset

5th fault within

60' interval, man‐

ual reset

Compressor 4 A4 heat

switches (YCSA/LCA

150, YCSA-H/BRAW

150)

ID13

-

Comp 4

-

-

-

AUTO/

MANUAL

6th fault within 60'

interval, automatic

reset

6th fault within

60' interval, man‐

ual reset

Circ. 1 high-pressure

switch HP1

ID6

X

-

Circ. 1

-

-

AUTO/

MANUAL

 

manual

reset

Circ. 2 high-pressure

switch HP2

ID11

-

X

Circ. 2

-

-

AUTO/

MANUAL

 

manual

reset

Circ. 1 high-pressure

switch LP1

ID5

X

-

Circ. 1

-

-

AUTO/

MANUAL

 

manual

reset

Circ. 2 high-pressure

switch LP2

ID10

-

X

Circ. 2

-

-

AUTO/

MANUAL

 

manual

reset

Circ. 1 high-pressure

switch by transducer

B3

X

-

Circ. 1

-

-

MANUAL

 

manual

reset

Circ. 2 high-pressure

switch by transducer

B4

-

X

Circ. 2

-

-

MANUAL

 

manual

reset

B3 probe faulty

B3

X

X

X

X

X

MANUAL

60'

 

B4 probe faulty

B4

X

X

X

X

X

MANUAL

60'

 

B5 probe faulty

B5

 

 

 

 

 

MANUAL

60'

 

B6 probe faulty

B6

 

 

 

 

 

MANUAL

60'

 

B7 probe faulty

B7

 

 

 

 

 

MANUAL

60'

 

B8 probe faulty

B8

 

 

 

 

 

MANUAL

60'

 

Pump 1 maintenance

System

 

 

 

 

 

MANUAL

 

Set period in

Compressor

menu

Pump 2 maintenance

System

 

 

 

 

 

MANUAL

 

Set period in

Compressor

menu

Compressor 1

maintenance

System

 

 

 

 

 

MANUAL

 

Set period in

Compressor

menu

Compressor 2

maintenance

System

 

 

 

 

 

MANUAL

 

Set period in

Compressor

menu

Compressor 3

System

 

 

 

 

 

MANUAL

 

Set period in

Compressor

menu

1

User manual

1.1

General description of the unit

22

Содержание YORK YLCA 100

Страница 1: ...Air condensed water chillers and heat pumps YLCA YLHA 100 120 and 150 User manual Ref N 40291_EN 0112...

Страница 2: ...cription of the unit 2 1 1 1 Models available and capacities 2 1 1 2 Technical specifications 4 1 1 3 Operating instructions C3 YLCA YLHA 100 120 and 150 7 1 1 4 Regular maintenance activities for whi...

Страница 3: ...1 User manual...

Страница 4: ...Cool only model YLCA 40 YLCA 50 YLCA 60 YLCA 80 YLCA 100 YLCA 120 YLCA 150 Cooling ca pacity 1 39 3 51 8 60 1 72 1 100 3 118 5 150 5 Cooling ca pacity 2 39 6 52 1 60 5 72 6 101 119 151 1 Net cooling...

Страница 5: ...User manual 1 General description of the unit 1 1 3...

Страница 6: ...panded within the fin assembly Fans Of the axial and low sound level type Equipped with single phase motors with IP54 protection These motors allow speed control by means of a phase cut out shifter co...

Страница 7: ...program models 100 120 and 150 Water filter Supplied as a standard element on units including the hydro kit Stainless steel mesh with 1 mm diameter perforations Optional on units not including the hyd...

Страница 8: ...d and dimensioned in accordance with the load to be supported The antivibratory support accessory for models YLCA YLHA 40 50 and 60 includes 4 units whereas for models YLCA YLHA 80 100 120 and 150 inc...

Страница 9: ...uit 1 HP1 ID7 J4 1 Thermal protector compressor 1 THPC1 ID8 J4 9 Thermal protector compressor 2 THPC2 ID9 J4 2 Thermal protector circuit 1 fans THPF 1 2 ID10 J4 10 Low pressure switch circuit 2 LP2 ID...

Страница 10: ...screen and six keys with the following functions Alarm 2 Programming 1 Esc Escape Up 3 Enter 4 Down 5 The following functions can be selected from this screen ON OFF COLD HEAT Read the unit status Acc...

Страница 11: ...and lockout functions of the system by excessively high pressure NTC probes B5 and B6 B5 For the detection and control of water inlet temperature cool only and heat pump units B6 For the detection of...

Страница 12: ...ion comp 3 Protection comp 4 K RS 485 serial connection Z H1 HP1 HP2 High pressure switch L Phase board power supply C1 Fan 3 4 M General protection D1 Fan 1 2 N Neutral board power supply F1 Fan prot...

Страница 13: ...ssword display press ENTER 2 Enter the password using the Up key 3 Press ENTER to access the 4th Menu display 4th display MENU From this display we can access a set of submenus that provide informatio...

Страница 14: ...0 bar 0 Probe B3 configuration Maximum value 30 151 bar 45 Probe B4 configuration Minimum value 30 152 bar 0 Probe B4 configuration Maximum value 30 153 bar 45 A Antifreeze Description Range Units Val...

Страница 15: ...hours for compressor 2 circuit 2 maintenance alarm 1000 999000 Hours 0 x 1000 Tandem compressor rotation time Minutes 20 Enabling of compressors C1 1 C2 1 C1 2 C2 2 YES NO YES Forced manual compresso...

Страница 16: ...orating pressure differential in summer cycle 0 99 9 bar 1 5 Min fan speed differential 99 9 99 9 bar 3 Max inverter speed 0 10 V 10 Min inverter speed 0 10 V 1 Inverter speed up time 0 999 Seconds 5...

Страница 17: ...ALWAYS ON No of hours for pump rotation 0 9999 Hours 12 ON OFF digital input activation YES NO NO WINTER SUMMER digital input activation YES NO NO ON OFF activation with Monitor YES NO NO WINTER SUMM...

Страница 18: ...ure switch circuit 2 O C 0 OPEN C CLOSED Digital input 12 Thermal protector compressor 3 circuit 2 O C 0 OPEN C CLOSED Digital input 13 Thermal protector compressor 4 circuit 2 O C 0 OPEN C CLOSED Dig...

Страница 19: ...Alarm selection with automatic reset high pressure switch AUTOMATIC MANUAL AUTOMATIC r Control When this submenu is activated the dynamic set point temperature appears if this function is enabled Pres...

Страница 20: ...behaviour is similar but affected by al algorithm that takes time into account integration time parameter STPM Set point A Cool B Heat RBM Control band EWT Exchanger inlet temperature C1 C2 C3 C4 Comp...

Страница 21: ...ff a compressor in the tandem of the affected circuit The parameters of said function are accessed from the CONDENSATION menu Defrost cycle If the evaporating pressure of one of the systems remains be...

Страница 22: ...water temperature has reached said value plus a preestablished differential said output will be deactivated see parameters in the ANTIFREEZE menu Remote ON OFF A digital ON OFF remote input can be in...

Страница 23: ...e this function from the H unit config menu The system has two monitoring protocols Carel and Modbus AUTO RESTART When the unit is turned off by a power shortage and once this has been restored the un...

Страница 24: ...h fault within 60 interval man ual reset Compressor 3 A3 heat switches YCSA LCA 150 YCSA H BRAW 150 ID12 Comp 3 AUTO MANUAL 5th fault within 60 interval automatic reset 5th fault within 60 interval ma...

Страница 25: ...an Off pump Off sys Reset Delay Notes maintenance Compressor 4 maintenance System MANUAL Set period in Compressor menu No link Display CHECK CABLE CONFIGURE No MCH3 com munication and display User man...

Страница 26: ...12 16 55 46 4 74 80 1 66 21 71 07 13 15 9 47 4 59 81 1 62 20 67 74 14 15 28 48 4 44 82 1 57 19 64 54 15 14 68 49 4 3 83 1 53 18 61 62 16 14 12 50 4 16 84 1 49 17 58 66 17 13 57 51 4 02 85 1 45 1 1 4...

Страница 27: ...d safety regulations and procedures applicable to HVAC units They should also be aware of general procedures and those applying specifically to this unit Contact a Johnson Controls Inc Authorised Tech...

Отзывы: