-/- Configuration of probes
Description
Range
Units
Value
Probe B3 calibration.
Coil pressure circuit 1
-9,9/9,9
bar
0
Probe B4 calibration.
Coil pressure circuit 2
-9,9/9,9
bar
0
Probe B5 calibration.
Inlet water temp. to exchanger.
-9,9/9,9
°K
0
Probe B6 calibration.
Outlet water temp. to exchanger.
-9,9/9,9
°K
0
Probe B7 calibration.
Outdoor temperature
-9,9/9,9
°K
0
Probe B8 calibration.
Dynamic set point
-9,9/9,9
%
0
Enabling probe B1
YES/NO
-
NO
Enabling probe B2
YES/NO
-
NO
Enabling probe B3.
Coil pressure circuit 1
YES/NO
-
YES
Enabling probe B4.
Coil pressure circuit 2
YES/NO
-
YES
Enabling probe B5.
Inlet water temp. to exchanger.
YES/NO
-
YES
Enabling probe B6.
Outlet water temp. to exchanger.
YES/NO
-
YES
Enabling probe B7
YES/NO
-
NO
Enabling probe B8
YES/NO
-
NO
Enabling probe B9.
YES/NO
-
NO
Enabling probe B10.
YES/NO
-
NO
Probe B3 configuration.
Minimum value
-30/150
bar
0
Probe B3 configuration.
Maximum value
-30/151
bar
45
Probe B4 configuration.
Minimum value
-30/152
bar
0
Probe B4 configuration.
Maximum value
-30/153
bar
45
-A- Antifreeze
Description
Range
Units
Value
Antifreeze alarm set point
-99,9/99,9
°C
3
Antifreeze alarm set point differential
99,9
°K
5
Lower antifreeze alarm set point limit
-99,9/99,9
°C
3
Upper antifreeze alarm set point limit
-99,9/99,9
°C
5
Antifreeze alarm reset
MANUAL
AUTOMATIC
-
MANUAL
Antifreeze alarm delay (If automatic reset has been selected)
0/540
Minutes
0
Antifreeze heater trigger set point
-99,9/99,9
°C
3
Antifreeze heater trigger set point differential
-99,9/99,9
°K
2
Auxiliary heater trigger set point (winter cycle)
-99,9/99,9
°C
25
Auxiliary heater trigger set point differential (winter cycle)
-99,9/99,9
°K
5
Auxiliary heater trigger delay
0/60
Minutes
15
Automatic enabling of the frost protection system with the unit OFF
DISABLED
HEATER AND PUMP
HEATER AND UNIT HEATER
-
HEATER AND PUMP
(YLCA)
HEATER AND UNIT
HEATER (YLHA)
1
User manual
1.1
General description of the unit
12