-F- Condensation (fans)
Description
Range
Units
Value
Type of fan control
Temp. pressure ON/OFF
-
Pressure
No. of condensers
1-2
-
2
Control device
Fans
-
Inverter
Inverter
-
Power supply frequency
50 / 60
Hz
50
PWM max. triac cut-off
0 / 100
%
92
PWM min. triac cut-off
0 / 100
%
35
Triac impulse duration
0 / 10
ms
2
Condensing pressure in summer cycle
0 / 99,9
bar
21
Condensing pressure differential in summer cycle
0 / 99,9
bar
5
Evaporating pressure in winter cycle
0 / 99,9
bar
9,5
Evaporating pressure differential in summer cycle
0 / 99,9
bar
1,5
Min. fan speed differential
-99,9 / 99,9
bar
3
Max. inverter speed
0 / 10
V
10
Min. inverter speed
0 / 10
V
1
Inverter speed-up time
0 / 999
Seconds
5
Prevent function activation (HP)
YES/NO
-
YES
Selection of probe for HP prevention
Pressure
-
Pressure
Temperature
HP prevention pressure
-99,9 / 99,9
bar
38
HP prevention pressure differential
0 / 99,9
bar
4
LP prevention pressure
-99,9 / 99,9
bar
3
LP prevention pressure differential
0 / 99,9
bar
1,5
Fan management in case of probe failure
Fan OFF
Fan OFF
Fan ON and Compressor ON
Prevent function timing
0 / 99
Seconds
0
1
User manual
1.1
General description of the unit
14