-P- Alarms
Description
Range
Units
Value
High-pressure alarm set point (transducer B3; B4)
0 / 99,9
bar
41
High-pressure alarm differential (transducer B3; B4)
0 / 99,9
bar
10
Summer low-pressure alarm
0 / 99,9
bar
3
Winter low-pressure alarm
0 / 99,9
bar
2
Defrost low-pressure alarm
0 / 99,9
bar
1
Low-pressure differential
0 / 99,9
bar
1
Low-pressure alarm delay on cold cycle start-up
0 ‑ 999
Seconds
60
Low-pressure alarm delay on heat cycle and defrost
0 ‑ 999
Seconds
0
Water flow control (flow switch) alarm delay on start-up
0 ‑ 999
Seconds
20
Water flow control (flow switch) alarm delay on operating
0 ‑ 9999
Seconds
5
Number of automatic reset alarm stoppages
0 ‑ 4
1
Maximum period for automatic reset alarms
0 ‑ 99
Minutes
60
Alarm selection with automatic reset: compressor thermal breaker
AUTOMATIC
/ MANUAL
AUTOMATIC
Alarm selection with automatic reset: fan thermal breaker
AUTOMATIC
/ MANUAL
AUTOMATIC
Alarm selection with automatic reset: low-pressure switch
AUTOMATIC
/ MANUAL
AUTOMATIC
Alarm selection with automatic reset: high-pressure switch
AUTOMATIC
/ MANUAL
AUTOMATIC
-r- Control
When this submenu is activated, the dynamic set point temperature appears (if this function is enabled).
Press Down to access the configuration menu.
Description
Range
Units
Value
Set point in COOL
°C
12
Set point in HEAT
°C
40
Temperature control adjustment range
°K
3
COOL set point lower limit
°C
6
COOL set point upper limit
°C
20
HEAT set point lower limit
°C
25
HEAT set point upper limit
°C
45
Temperature setting type
INPUT / OUTPUT
-
INPUT
Setting type with input probe
PROPORTIONAL / P+I
PROPORTIONAL
Integration time in each adjustment P+I
0 / 9999
Seconds
600
Max. increase time of call (output adjustment)
0 / 9999
Seconds
20
Min. increase time of call (output adjustment)
0 / 9999
Seconds
20
Max. decrease time of call (output adjustment)
0 / 9999
Seconds
10
Min. decrease time of call (output adjustment)
0 / 9999
Seconds
10
Temp. differential in which increase and decrease times vary
(output adjustment)
-99,9 / 99,9
°C
2
Forced stoppage in COOL cycle (output adjustment)
-99,9 / 99,9
°C
5
Forced stoppage in HEAT cycle (output adjustment)
-99,9 / 99,9
°C
47
User manual
1
General description of the unit
1.1