TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan

Control Installation Instructions

15

Troubleshooting

See Table 6 for alarm messages. See Table 7 for 
further troubleshooting details.

Accessories

All the optional accessories in Table 5 include mounting 
hardware; contact the nearest Johnson Controls® 
representative to order any of these parts.

Note:

Review the technical specifications of the 

optional accessories prior to their use in an application.

Repair Information

If the TEC2145-4 Thermostat Controller fails to operate 
within its specifications, replace the unit. For a 
replacement thermostat controller, contact the nearest 
Johnson Controls representative.       

Aux cont

Determines the auxiliary contact 
function and configuration.
Default: 

0

(0)

Not used, 
or used for 
reheat

If the sequence is set to reheat (2, 3, or 5), 
ignore this parameter.

(1)

Auxiliary 
N.O.

Occupied = contact 
closed
Unoccupied = contact 
open

The output 
aligns with 
occupancy.

(2)

Auxiliary 
N.C.

Occupied = contact open
Unoccupied = contact 
closed

(3)

Auxiliary 
N.O.

Occupied and fan On = 
contact closed
Unoccupied and fan On 
or Off = contact open

The output 
aligns with 
occupancy 
and the fan 
on command.

(4)

Auxiliary 
N.C.

Occupied and fan On = 
contact open
Unoccupied and fan On 
or Off = contact closed

(5)

This selection option is not used.

DA/RA

Choice of direct or reverse acting 
analog output signal.
Default: 

DA

(RA):

 Reverse acting, 0 to 100% = 10 to 0 VDC

(DA):

 Direct acting, 0 to 100% = 0 to 10 VDC

Reheat

Sets the duty cycle time for the 
reheat output (if Option 2, 3, or 5 is 
chosen in the 

SeqOpera

 

parameter).
Default: 

0

(1):

 10 seconds (six cycles per minute), for various equipment with 

solid-state relays that withstand short duty cycles such as electric 
heat.

(0):

 15 minutes (four cycles per hour), for various equipment with 

mechanical relays or contactors controlling mechanical reheat 
systems.

UI3 dis

Displays the supply or changeover 
temperature when UI3 is configured 
as an analog input (SS or COS). 
Used as a diagnostic/service help, 
to troubleshoot and diagnose 
sensor operation.
Default: 

-40°F/-40°C

Not applicable

1.

This parameter functions only when the TEC is used in conjunction with an onboard occupancy sensor, or a remote 
occupancy sensor.

Table 4:  Installer Configuration Menu  (Part 6 of 6)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...