background image

TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan 
Control Installation Instructions

8

If there is a Relinquish Default for the setpoints, the 
NAE always has an Override for either an adjusted 
value or the Relinquish Default Value. You should use 
Operator Override and Release Operator Override if 
you want to command the setpoint and release it to 
local control.

Once all the NAE commands are released, the 
Override Status in the Hardware tab displays False. At 
that time, the user is can change the setpoint from the 
local display.

Setup and Adjustments 

Thermostat Controller User Interface Keys

The TEC2145-4 Thermostat Controller user interface 
consists of five keys on the front cover (Figure 6). The 
function of each key is as follows:

MODE

 key toggles among the system modes 

available, as defined by selecting the appropriate 
operation sequence in the Installer Configuration 
Menu (Off, Heat, Cool, Auto).

FAN

 key toggles among ON and AUTO for fan 

control. ON energizes the fan all the time and 
AUTO operates the fan only on a call for heating or 
cooling, for both occupied and unoccupied periods.

OVERRIDE

 key overrides the unoccupied mode to 

occupied at the local user interface for the 
specified TOccTime. (TOccTime is defined by 
selecting the appropriate time period in the Installer 
Configuration Menu.) If one of the binary inputs is 
configured to operate as a remote override contact, 
this 

OVERRIDE

 function is disabled. The 

OVERRIDE

 key also allows access to the Installer 

Configuration Menu. See 

Configuring the 

TEC2145-4 Thermostat Controller

.

UP/DOWN

 arrow keys change the configuration 

parameters and activate a setpoint adjustment.

Note:

If a setpoint is overridden through the 

N2 network, the setpoint appears 

so 

that it can be 

changed via the thermostat controller, but the setpoint 
is held at the overridden value. Locally entered 
setpoints revert to the N2 network settings with each 
change of schedule status.

Light-Emitting Diodes (LEDs)

Three System Activity LEDs are included to indicate 
the status and actions of the thermostat controller:

The fan LED 

 is on when the fan is on.

The heat LED 

 is on when heating is on.

The cool LED 

 is on when cooling is on.

Backlit LCD

The TEC2145-4 Thermostat Controller includes a 
2-line, 8-character backlit display. Low-level 
backlighting is present during normal operation, and it 
brightens when any user interface key is pressed. The 
backlight returns to low level when the thermostat 
controller is left unattended for 45 seconds.

Figure 6: Front Cover of Thermostat Controller

70.0ºF

Room Temp

FI

G

:T

E

C214

5_f

rn

tv

w

Five keys on the thermostat controller
make operation easy and intuitive.

Backlit, plain text

Liquid Crystal Display (LCD)

is easy to read in any condition.

Light-Emitting Diodes (LEDs)
indicate system activity.

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...

Отзывы: