TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan
Control Installation Instructions
9
Status Display Menu
The Status Display Menu is displayed during normal
thermostat controller operation. This menu
continuously scrolls through the following parameters:
•
Room Temperature
•
System Mode
•
Schedule Status (Occupied/Unoccupied/Override)
•
Applicable Alarms – The backlight lights up as an
alarm condition is displayed.
Note:
An option is available within the Installer
Configuration Menu to lock out the scrolling display and
show only the
Room Temperature
parameter.
Configuring the TEC2145-4 Thermostat
Controller
The TEC2145-4 Thermostat Controller comes from the
factory with default settings for all configurable
parameters. The default settings are shown in Table 4.
To reconfigure the parameters via the thermostat
controller, follow the steps in this section.
1.
To access the Installer Configuration Menu, press
and hold the
OVERRIDE
key for approximately
8 seconds.
Note:
If the
Password
parameter is configured,
Password 0 appears on the thermostat controller
display indicating that the configured password is
required to proceed. Use the
UP/DOWN
arrow
keys to indicate the configured password, then
press the
MODE
key to proceed through the
Installer Configuration Menu parameters.
2.
Once the Installer Configuration Menu begins,
press and release the
OVERRIDE
key to scroll
through the parameters listed in Table 4.
3.
When the desired parameter is displayed, use the
UP/DOWN
arrow keys to choose the desired
selection option.
4.
Press and release the
OVERRIDE
key to continue
scrolling through the parameters.
Note:
Pressing the
FAN
key during configuration
restarts the list of displayed parameters at the first
parameter listed in Table 4.
When the thermostat controller is in the Installer
Configuration Menu and left unattended for
approximately 8 seconds, the thermostat controller
reverts to the Status Display Menu.
Configuring Inputs BI1, BI2, and UI3
When BI1 and BI2 are configured for an alarm
condition, an alarm condition is displayed locally when
the input is closed. An alarm message is included on
the scrolling Status Display Menu and when the
message is displayed, the backlight momentarily
lights up.
The UI3 input provides changeover of hot/cold water
switching, or supply air temperature monitoring at the
thermostat controller.
Each input can be configured to the Selection Options
included in Table 4.
Configuring the Sequence of Operation
(SeqOpera)
Choose the appropriate sequence of operation. The
modes presented are user-dependent on the sequence
of operation selected. For applications using a
changeover sensor, choose the selection option
(0): Cooling Only
. Changeover occurs between
Cooling Only
and
Heating Only
. See Table 3 for
selection options, and Figure 7 through Figure 10 for
sequence of operation examples.
Table 3: Selection Options for Sequence of Operation
Selection Option
Control Curve
Terminal Numbers Used
(See Figure 5.)
0: Cooling Only
See Figure 7.
10:
Proportional Cooling
1: Heating Only
See Figure 8.
10:
Proportional Heating
2: Cooling and Reheat
See Figure 9.
6 and 7:
Reheat
10:
Proportional Cooling
3: Heating and Reheat
See Figure 10.
6 and 7:
Reheat
10:
Proportional Heating