TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan

Control Installation Instructions

9

Status Display Menu

The Status Display Menu is displayed during normal 
thermostat controller operation. This menu 
continuously scrolls through the following parameters:

Room Temperature

System Mode

Schedule Status (Occupied/Unoccupied/Override)

Applicable Alarms – The backlight lights up as an 
alarm condition is displayed.

Note:

An option is available within the Installer 

Configuration Menu to lock out the scrolling display and 
show only the 

Room Temperature

 parameter.

Configuring the TEC2145-4 Thermostat 
Controller

The TEC2145-4 Thermostat Controller comes from the 
factory with default settings for all configurable 
parameters. The default settings are shown in Table 4. 
To reconfigure the parameters via the thermostat 
controller, follow the steps in this section.

1.

To access the Installer Configuration Menu, press 
and hold the 

OVERRIDE

 key for approximately 

8 seconds.

Note:

If the 

Password

 parameter is configured, 

Password 0 appears on the thermostat controller 
display indicating that the configured password is 
required to proceed. Use the 

UP/DOWN

 arrow 

keys to indicate the configured password, then 
press the 

MODE

 key to proceed through the 

Installer Configuration Menu parameters.

2.

Once the Installer Configuration Menu begins, 
press and release the 

OVERRIDE

 key to scroll 

through the parameters listed in Table 4.

3.

When the desired parameter is displayed, use the 

UP/DOWN

 arrow keys to choose the desired 

selection option.

4.

Press and release the 

OVERRIDE

 key to continue 

scrolling through the parameters.

Note:

Pressing the 

FAN

 key during configuration 

restarts the list of displayed parameters at the first 
parameter listed in Table 4.

When the thermostat controller is in the Installer 
Configuration Menu and left unattended for 
approximately 8 seconds, the thermostat controller 
reverts to the Status Display Menu.

Configuring Inputs BI1, BI2, and UI3

When BI1 and BI2 are configured for an alarm 
condition, an alarm condition is displayed locally when 
the input is closed. An alarm message is included on 
the scrolling Status Display Menu and when the 
message is displayed, the backlight momentarily 
lights up.

The UI3 input provides changeover of hot/cold water 
switching, or supply air temperature monitoring at the 
thermostat controller.

Each input can be configured to the Selection Options 
included in Table 4. 

Configuring the Sequence of Operation 
(SeqOpera)

Choose the appropriate sequence of operation. The 
modes presented are user-dependent on the sequence 
of operation selected. For applications using a 
changeover sensor, choose the selection option 

(0): Cooling Only

. Changeover occurs between 

Cooling Only

 and 

Heating Only

. See Table 3 for 

selection options, and Figure 7 through Figure 10 for 
sequence of operation examples.   

Table 3:  Selection Options for Sequence of Operation 

Selection Option

Control Curve

Terminal Numbers Used
(See Figure 5.)

0: Cooling Only

See Figure 7.

10: 

Proportional Cooling

1: Heating Only

See Figure 8.

10:

 Proportional Heating

2: Cooling and Reheat

See Figure 9.

6 and 7:

 Reheat

10:

 Proportional Cooling

3: Heating and Reheat

See Figure 10.

6 and 7:

 Reheat

10: 

Proportional Heating

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...

Отзывы: