TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan 
Control Installation Instructions

14

Set type

Provides the option of temporarily 
changing the heating or cooling 
setpoint by pressing the 

UP/DOWN

arrow keys.

Default: 

permnent

(temporar):

 Local changes to the heating or cooling setpoints are 

temporary, and remain effective for the specified TOccTime.

(permnent):

 Local changes to the heating or cooling setpoints are 

permanently stored in the thermostat controller memory.

Spt Func

Determines the operation and 
usage of the local setpoint interface 
by the user.
Default: 

Dual Stp

(Attch Stp):

 Single Occupied Setpoint Adjustment. The displayed 

setpoint is the setpoint from the last action taken by the thermostat 
controller, or the setpoint currently in use. Both the heating and 
cooling setpoints are changed simultaneously, while respecting the 
minimum configured deadband. If one setpoint is desired over the 
other, use the 

MODE

 key to toggle between the two setpoints.

(Dual Stp):

 Dual Occupied Setpoint Adjustment. The displayed 

setpoint is the setpoint from the last action taken by the thermostat 
controller, or the setpoint currently in use. The heating and cooling 
setpoints can be separated individually, allowing the minimum 
configured deadband to expand. If one setpoint is desired over the 
other, use the 

MODE

 key to toggle between the two setpoints.

TOccTime

Sets the duration of the Temporary 
Occupancy Time when the heating 
or cooling setpoints in the Occupied 
mode are established by:
• 

an Override Function enabled in 
the Main User Menu (when the 
thermostat controller is in the 
Unoccupied mode)

• 

a temporary heating or cooling 
setpoint

Default: 

2.0 hrs

Range: 

0.0 

to

 24.0 hrs

 (adjustable in 1-hour increments)

Deadband

Sets the minimum deadband 
between the heating and cooling 
setpoints.
Default: 

2.0F°/1.0C°

Range: 

2.0F°/1.0C° 

to

 5.0F°/2.5C°

 (adjustable in 1.0F°/0.5C° 

increments)

Cal RS

Sets the desired room air sensor 
calibration (offset). The offset can 
be added to or subtracted from the 
actual displayed room temperature.
Default: 

0.0F°/0.0C°

Range: 

-5.0F°/-2.5C° 

to

 5.0F°/2.5C°

 (adjustable in 1.0F°/0.5C° 

increments)

Table 4:  Installer Configuration Menu  (Part 5 of 6)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...

Отзывы: