TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan 
Control Installation Instructions

16

Table 5:  Accessories (Order Separately)

Code Number

Description

TEC-6-PIR

1

Commercial Fan Coil Controller Cover with Occupancy Sensor

TE-6361M-1

2

Duct Mount Air Temperature Sensor

TE-636S-1

Strap-Mount Temperature Sensor

SEN-600-4

3

Remote Indoor Air Temperature Sensor with Occupancy Override and LED

1.

The TEC-6-PIR Accessory Cover can be used to replace the existing cover on a non-PIR TEC2145-4 Thermostat 
Controller to provide occupancy sensing capability.

2.

Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the 

TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320)

 for more details.

3.

The occupancy override function can only be accomplished using the SEN-600-4 with the TEC2145-4.

Table 6:  Alarm Messages

Display

Function

Service

Indicates that there is a service alarm in accordance with the programmable Binary Input (BI2).

Filter

Indicates that the filter(s) is dirty in accordance with the programmable Binary Input (BI2).

Window

Indicates that an outside window or door is open and has cancelled the thermostat controller 
heating or cooling action in accordance with the programmable Binary Input (BI1).

Table 7:  Troubleshooting Details

Error/Trouble 
Condition

Probable Cause

Solution

Thermostat 
Controller Cycles 
Online and Offline

Two or more controllers have the same 
address.

Change each duplicate address to a unique number.

There are Y or T taps on the N2 Bus, or 
the repeater has lost power or is wired 
incorrectly.

Refer to the 

N2 Communications Bus Technical Bulletin 

(LIT-636018).

Thermostat 
Controller Does 
Not Come Online

Two or more controllers have the same 
address.

Change each duplicate address to a unique number.

The N2 Bus contains too many devices.

Do not exceed the maximum number of devices allowed on 
the N2 Bus per supervisory controller limitations.

The thermostat controller does not have 
power.

Apply power to the thermostat controller.

The N2 cable runs are broken.

Locate the break and correct the wiring.

The thermostat controller device type is 
incorrect.

Change the thermostat controller device type to VND.

N2 Bus is Offline

The wiring on the N2 Bus is broken.

Repair the wiring.

No point mapping has been entered.

Define the BAS dataset.

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...

Отзывы: