TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan

Control Installation Instructions

11

BI1

Configuration of Binary Input 1.
Default: 

None

(None):

 No function is associated with an input.

(Rem NSB):

 Remote Night Setback (NSB) via a time clock input, an 

occupancy sensor, or from a voltage-free contact. 
Contact open = Occupied; contact closed = Unoccupied.

(MotionNO*):

 Temporary occupancy request via a motion detector 

input. Contact open = Unoccupied. When the contact closes, the 
thermostat controller goes into the occupied mode for a specified 
TOccTime. Once the TOccTime begins, the thermostat controller 
remains in the occupied mode if the contact is open, until the 
TOccTime expires.

(MotionNC*):

 Temporary occupancy request via a motion detector 

input. Contact closed = Unoccupied. When the contact opens, the 
thermostat controller enters occupied mode for a specified 
TOccTime. Once the TOccTime begins, the thermostat controller 
remains in the occupied mode if the contact is closed, until the 
TOccTime expires.

(Window**):

 Cancels the thermostat controller heating or cooling 

action when a window is open. A Window alarm is displayed 
indicating that the window needs to be closed to resume heating or 
cooling.
* These settings disable any local override function.
**When this setting is selected, the heating and/or cooling outputs 
are enabled only when the contact is closed. If the fan is set to Auto, 
it is enabled only when the contact is closed. If the fan is set to On, it 
is not affected by this setting.

BI2

Configuration of Binary Input 2.
Default: 

None

(None):

 No function is associated with an input.

(Door Dry): 

Door contact only has an effect if BI1 is set to MotionNO 

or MotionNC. (See the BI1 parameter listed previously in this table.) 
The occupancy is now dictated via BI1 and BI2. Any motion 
detected sets the zone to Occupied status. The zone remains 
permanently in occupied mode until the door contact switch opens 
momentarily. The thermostat then enters stand-by mode. If more 
movements are detected, the occupied mode resumes. While the 
door is opened, any movements detected by the remote PIR sensor 
or the PIR accessory cover are ignored. Use a Normally Closed 
contact switching device. Contact opened = Door opened, 
Contact closed = Door closed.

(RemOVR):

 Temporary occupancy request via a remote input. This 

override function is controlled by a manual remote occupancy 
override. When enabled, this condition disables the override 
capability of the thermostat controller.

(Filter):

 A Filter alarm is displayed. This alarm can be connected to 

a differential pressure switch that monitors a filter.

(Service):

 A Service alarm is displayed on the thermostat controller 

when the input is energized. This input can be tied into the air 
conditioning unit control card, which provides an alarm should there 
be a malfunction.

Table 4:  Installer Configuration Menu  (Part 2 of 6)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...

Отзывы: