TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan

Control Installation Instructions

7

Connecting the N2 Bus

To connect the N2 Bus:

1.

Set the N2 address of the TEC2145-4 Thermostat 
Controller per the engineering drawings prior to 
wiring the thermostat controller. (See the 

Com 

addr

 parameter in Table 4 to set the N2 address for 

the thermostat controller.) Also, test for N2 voltage, 
polarity, and isolation prior to wiring the thermostat 
controller.

Note:

Pressing and holding the 

UP/DOWN

 arrow 

keys simultaneously displays the device address 
that is assigned.

2.

Observe the polarity when connecting the N2 Bus 
wires to the thermostat controller.

3.

After the N2 Bus wires are connected to the first 
thermostat controller, continue in a daisy-chained 
fashion to the next thermostat controller.

Note:

The N2 Bus wiring must be twisted-pair 

lines. Do not run the N2 Bus wiring in the same 
conduit as line voltage wiring (30 VAC or above) or 
other wiring that switches power to highly inductive 
loads (such as contactors, coils, motors, or 
generators).

For more N2 Bus overview information, refer to the 

N2 Communications Bus Technical Bulletin 
(LIT-636018)

 and the 

ASC and N2 Bus Networking and 

Troubleshooting Guide Technical Bulletin 
(LIT-6363003)

.

N2 Write, Override, and Release Commands

N2 overrides take priority over any local adjustment or 
command in the thermostat controller until the override 
is released. For example, if the supervisory controller 
sends an N2 override message to turn System Mode 
Off and then the user selects System Mode On at the 
thermostat controller keypad, the thermostat controller 
keeps the System Mode Off.

When an N2 override is released, the object may once 
again be changed through the thermostat controller 
keypad. The thermostat controller does not retain any 
data entered at the thermostat controller keypad during 
the override. 

The thermostat controller automatically releases all N2 
overrides after 10 minutes of no communications. For 
example, if the network cable is removed from the 
thermostat controller or if the supervisory controller 
goes offline.

The thermostat controller does not maintain an internal 
command priority table. The most recent command 
received by any of the Object Types listed in Table 2 
controls the thermostat controller. 

However, if the Metasys system sends an N2 write 
command to turn System Mode Off and the user 
selects System Mode On at the thermostat controller 
keypad, the thermostat controller keeps the System 
Mode On.

Handling Setpoints

If a setpoint is overridden, the thermostat controller 
adjusts the other setpoint to maintain the minimum 
deadband between the setpoints, if necessary. The 
setpoints can be spread farther apart but can never be 
adjusted closer than the current minimum deadband 
value.

The value for Heating SP (ADI-3), Unoccupied 
Heating SP (ADI-5), and Standby Heating SP 
(ADI-10) must stay within the limits for Minimum 
Heat SP (40°F / 4.5°C) and Maximum Heat SP 
(ADI-14).

The value for Cooling SP (ADI-4), Unoccupied 
Cooling SP (ADI-6), and Standby Cooling SP 
(ADI-11) must stay within the limits established in 
the controller by Minimum Cool SP (ADI-15) and 
Maximum Cool SP (100°F / 37.5°C).

Failure to stay within the limits for a command results in 
an N2 Negative Acknowledgment (NAK) error from the 
thermostat controller.

N2 Device Mapping

Metasys® System Person-Machine Interface (PMI)

Define the N2 thermostat controller as a Vendor Device 
(VND) when adding the thermostat controller to the 
supervisory controller. 

Do not direct-map any points; instead, run control of 
these points through the Control System (CS) object. 
The supervisory controller Model Point Type is the 
definition inside the model file. Use a CS object to 
retrieve the data.

Metasys System Extended Architecture

The Controller Point Type is the fixed-point definition 
inside the controller. Refer to the 

N2 Integration with 

the NAE Technical Bulletin (LIT-1201683)

 for more 

information on Controller Point Types.

Network Automation Engine (NAE) Setpoint 
commands translate into N2 Write commands. NAE 
Operator Override and Release Operator Override 
translate into N2 Override and Release commands, 
respectively.

You must not have a Relinquish Default for the 
setpoints if you want to change them from the 
thermostat controller display.

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...

Отзывы: