TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and One-Speed Fan

Control Installation Instructions

13

St-By TM

1

Sets stand-by timer value; time 
delay between moment where 
occupancy sensor detected the last 
movement in the area and the time 
which the thermostat stand-by mode 
and setpoints become active.
Default: 

0.5 hours

Range: 

0.5

 to 

24.0

 

hours

, in 0.5 hour increments

Unocc TM

1

Sets Unoccupied Timer Value; time 
delay between the moment where 
the thermostat controller toggles to 
stand-by mode and the time which 
the thermostat controller 
unoccupied mode and setpoints 
become active.
Default: 

0.0

 hours

0.0 hours 

or Factory Value: Setting this parameter to its default 0 

value disables the occupied timer and prevents the thermostat 
controller from drifting from stand-by mode to unoccupied mode 
when occupancy sensor functions are used.
Range: 

0.0 

to 

24.0

 

hours

 in 0.5 hour increments.

St-By HT

1

Sets Stand-by heating setpoint; 
value is between occupied and 
unoccupied heating setpoints.
Default:

 69.0°F/20.6°C

Range: 

40.0°F/4.5°C

 to 

90.0°F/32.0°C

Note:

When adjusting 

the temperature, press the 

UP/DOWN

 arrow keys to 

change the temperature in 
0.5F°/0.5C° increments; 
press and hold the 

UP/DOWN

 arrow keys 

to change the temperature 
in 5.0F°/5.0C° increments.

St-By CL

1

Sets Stand-by cooling setpoint limit; 
value is between occupied and 
unoccupied cooling setpoints.
Default: 

78.0°F/25.6°C

Range: 

54.0°F/12.0°C

 to 

100.0°F/37.5°C

Unocc HT

Sets the Unoccupied Heating 
setpoint value.
Default: 

62.0°F/16.5°C

Range: 

40.0°F/4.5°C 

to

 

90.0°F/32.0°C

Unocc CL

Sets the Unoccupied Cooling 
setpoint value.
Default: 

80.0°F/26.5°C

Range: 

54.0°F/12.0°C 

to

100.0°F/37.5°C

Heat max

Sets the Occupied and Unoccupied 
maximum Heating setpoint values.
Default: 

90.0°F/32.0°C

Range: 

40.0°F/4.5°C 

to

90.0°F/32.0°C

Cool min

Sets the Occupied and Unoccupied 
minimum Cooling setpoint values.
Default: 

54.0°F/12.0°C

Range: 

54.0°F/12.0°C 

to

100.0°F/37.5°C

Pband

Proportional Band used by the PI 
temperature control loop of the 
thermostat controller.
Pband is not converted with C or F 
scale and is always shown with a 
range of 3 to 10.
Default: 

3

 (

3F°/1.7C°

)

Value

F Scale Pband/C Scale Pband

3

3.0F°/1.7C°

4

4.0F°/2.2C°

5

5.0F°/2.8C°

6

6.0F°/3.3C°

7

7.0F°/3.9C°

8

8.0F°/4.4C°

9

9.0F°/5.0C°

10

10.0F°/5.6C°

Note:

The use of a larger proportional band is not to use the 

thermostat controller as a discharge air controller device. The use of 
a larger proportional band can be used to solve issues for flawed 
HVAC design with basic sizing and thermostat controller location 
errors that cannot be worked around.

Table 4:  Installer Configuration Menu  (Part 4 of 6)

Parameter 
Appearing 
on Display

Description and Default

Selection Options

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...

Отзывы: