TEC2145-4 N2 Networked Thermostat Controller with Single Proportional Output and

One-Speed Fan Control Installation Instructions

1

Applications

The TEC2145-4 Thermostat Controller is an 
N2 networked device that provides control of two-pipe 
fan coils, cabinet unit heaters, or other equipment 
using a proportional 0 to 10 VDC control input and 
one-speed fan control. 

The technologically advanced TEC2145-4 Thermostat 
Controller features a Building Automation System 
(BAS) N2 Bus communication capability that enables 
remote monitoring and programming for efficient space 
temperature control.

The TEC2145-4 Thermostat Controller features an 
intuitive User Interface (UI) with backlit display that 
makes setup and operation quick and easy. The 
thermostat controller also employs a unique, 
proportional control algorithm that virtually eliminates 
temperature offset associated with traditional, 
differential-based thermostat controllers.  

North American Emissions Compliance

United States

Canada

Installation

Location Considerations

Locate the TEC2145-4 Thermostat Controller:

on a partitioning wall, approximately 1.5 m (5 ft) 
above the floor in a location of average 
temperature

away from direct sunlight, radiant heat, outside 
walls, outside doors, air discharge grills, or 
stairwells; or from behind doors

away from steam or water pipes, warm air stacks, 
unconditioned areas (not heated or cooled), or 
sources of electrical interference

Note:

Allow for vertical air circulation to the 

TEC2145-4 Thermostat Controller.

IMPORTANT:

The TEC2145-4 Thermostat 

Controller is intended to provide an input to 
equipment under normal operating conditions. 
Where failure or malfunction of the thermostat 
controller could lead to personal injury or property 
damage to the controlled equipment or other 
property, additional precautions must be designed 
into the control system. Incorporate and maintain 
other devices, such as supervisory or alarm systems 
or safety or limit controls, intended to warn of or 
protect against failure or malfunction of the 
thermostat controller. 

This equipment has been tested and found to 
comply with the limits for a Class A digital device 
pursuant to Part 15 of the FCC Rules. These limits 
are designed to provide reasonable protection 
against harmful interference when this equipment is 
operated in a commercial environment. This 
equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in 
accordance with the instruction manual, may cause 
harmful interference to radio communications. 
Operation of this equipment in a residential area is 
likely to cause harmful interference, in which case 
the user will be required to correct the interference 
at his/her own expense.

This Class (A) digital apparatus meets all the 
requirements of the Canadian Interference-Causing 
Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte 
toutes les exigences du Règlement sur le matériel 
brouilleur du Canada.

TEC2145-4 N2 Networked Thermostat Controller with 
Single Proportional Output and One-Speed Fan Control

Installation Instructions

TEC2145-4

Part No. 24-9890-1184, Rev. —

Issued February 8, 2010

Содержание TEC2145-4

Страница 1: ...the TEC2145 4 Thermostat Controller IMPORTANT The TEC2145 4 Thermostat Controller is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the the...

Страница 2: ...hermostat controller mounting base so that the arrow on the base points upward to indicate the top of the thermostat controller Note If you need to install the thermostat on an electrical junction box...

Страница 3: ...into the terminals be sure to properly twist the wires together prior to inserting them into the terminal connectors CAUTION Risk of Electric Shock Disconnect power supply before making electrical con...

Страница 4: ...0 to 10 VDC 24 VAC Com Analog Output and Valve 24 V Hot AO1 Fan Power and Fan BO5 Aux BO5 Aux Aux Contact Isolated Common Reheat Lighting On Off Actuation Exhaust Fan REF Supervisory Controller BI2 U...

Страница 5: ...upply Air Temperature Change Over Temp UI3 ADI 9 N2 AI CSAD 40 0 F 40 0 C to 122 0 F 50 0 C Standby Heating SP1 2 ADI 10 N2 AO CSAD 40 0 F 4 5 C to 90 0 F 32 0 C Standby Cooling SP1 2 ADI 11 N2 AO CSA...

Страница 6: ...orresponding cooling heating setpoint to maintain the minimum deadband between the two setpoints 3 The TEC2145 4 does not support an Outdoor Air Temperature sensor The supervisory controller writes th...

Страница 7: ...m the thermostat controller or if the supervisory controller goes offline The thermostat controller does not maintain an internal command priority table The most recent command received by any of the...

Страница 8: ...period in the Installer Configuration Menu If one of the binary inputs is configured to operate as a remote override contact this OVERRIDE function is disabled The OVERRIDE key also allows access to...

Страница 9: ...keys to choose the desired selection option 4 Press and release the OVERRIDE key to continue scrolling through the parameters Note Pressing the FAN key during configuration restarts the list of displa...

Страница 10: ...clng_wth_rht Deadband Reheat On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 9 Cooling with Reheat Temperature Increase Increments of 1F 0 5C FIG htg_wth_rh...

Страница 11: ...contact is closed If the fan is set to Auto it is enabled only when the contact is closed If the fan is set to On it is not affected by this setting BI2 Configuration of Binary Input 2 Default None No...

Страница 12: ...The scroll is active AutoMode Enables the Auto function if Cooling with Reheat is chosen in the SeqOpera parameter to be visible within the MODE key menu The MODE key is the key at the far left of th...

Страница 13: ...mperature in 5 0F 5 0C increments St By CL1 Sets Stand by cooling setpoint limit value is between occupied and unoccupied cooling setpoints Default 78 0 F 25 6 C Range 54 0 F 12 0 C to 100 0 F 37 5 C...

Страница 14: ...Setpoint Adjustment The displayed setpoint is the setpoint from the last action taken by the thermostat controller or the setpoint currently in use The heating and cooling setpoints can be separated...

Страница 15: ...and fan On contact closed Unoccupied and fan On or Off contact open The output aligns with occupancy and the fan on command 4 Auxiliary N C Occupied and fan On contact open Unoccupied and fan On or Of...

Страница 16: ...dance with the programmable Binary Input BI2 Window Indicates that an outside window or door is open and has cancelled the thermostat controller heating or cooling action in accordance with the progra...

Страница 17: ...ommended Thermostat Controller Measurement Range 40 0 F 40 0 C to 122 0 F 50 0 C Sensor Type Local 10k ohm Johnson Controls Type II Negative Temperature Coefficient NTC Thermistor Sensor Resolution 0...

Отзывы: