Maestro Software
64
Unit #3 Generic I/O
Setp:
Stat:
Inputs
Outputs
Schedules
A-Out
Usage
Next
Prev
#1
Undo
0
Target:
0
Deadband:
0
Gain:
0
High percent:
0
Low percent:
0
Scan rate [Sec]:
Control Input
Analog Output Setpoints
NONE
NONE
Water Heater Te
Input #2
Input #3
Input #4
Input #5
Input #6
Input #7
Input #8
Input #9
Input #10
Input #11
Control Input:
This area
lets you choose an input to
be associated with this
analog output.
Target:
This is the input value that the analog output is
trying to maintain.
Deadband:
This is the value above or below the target
during which the output does not change.
Gain:
This is the magnitude of change in the output caused
by a change in the input.
High Percent:
This defines the high end of the analog
output in either volts or mA. (A jumper on the ACT2
controller can be used to select either 0-10 volt or 4-20 mA
output.)
Low Percent:
This defines the low end of the analog output
in either volts or mA. (A jumper on the ACT2 controller can
be used to select either 0-10 volt or 4-20 mA output.)
Scan Rate:
This defines the frequency that the output
checks the input.
Figure 59: Analog Output Parameters