Maestro Software
56
Unit #3 Condensing Units
Setpoints:
Status:
Circuit
Compr.
Alarms
Condenser Defrost
#1
Next
Prev
Undo
Bd.
Heat:
Outputs:
Termination:
None
0
Pt.
Bd.
Liquid Line:
#2
2
Pt.
Bd.
None
0
Pt.
Digital
Open
0
Analog
22:00
Start 1:
04:00
Start 2:
00:00
Start 3:
00:00
Start 4:
00:00
Start 5:
00:00
Start 6:
20
Runoff:
Min
40
Duration:
Manual Defrost:
Defrost Start Times [HH:MM] :
Min
Defrost
Defrost
Runoff
Runoff
Terminate
Terminate
Defrost Start Times:
This section can be used to define up to six defrost start times. These
times must be given in the 24-hour clock format (e.g., 6:00 p.m. must be entered as 18:00).
Duration:
This defines
the maximum length of
the defrost cycle.
Runoff:
This defines the
dripping time after
defrost.
Manual Defrost:
These
three buttons are used to
manually begin a defrost
cycle, begin a runoff
cycle (dripping time), or
terminate a current
defrost cycle.
Termination:
Outputs:
This gives the I/O board location and type of defrost termination sensor.
This section defines the outputs that are controlled during defrost.
"Heat" output is
used to control an electric defrost heater, and the "Liquid Line" output is used to energize the
liquid line solenoid relay during defrost.
Figure 52: Refrigeration Circuit Defrost Parameters
Содержание PENN ACT2
Страница 16: ...Maestro Software 16 ...
Страница 30: ...Maestro Software 30 ...
Страница 38: ...Maestro Software 38 3 Click the unit you wish to view Figure 32 Select Unit Dialog 4 Click the OK button ...
Страница 90: ...Maestro Software 90 ...
Страница 102: ...Maestro Software 102 ...
Страница 104: ...Maestro Software 104 ...