© JBG-HT (v.2.0)
63
INSTRUCTION MANUAL
– HEAT PUMP
Code
Description
Type
Result
Modbus
AL190
Circuit 2 - Defrost interrupted by circuit alarm
Automatic reset
Message only
DI1114
AL191
Circuit 2 - Discharge pressure probe alarm
Automatic reset
Disconnecting
circuit 2
DI1115
AL192
Circuit 2 - Suction pressure probe alarm
Automatic reset
Disconnecting
circuit 2
DI1116
AL193
Circuit 2 - Discharge temperature probe alarm
Automatic reset
Disconnecting
circuit 2
DI1117
AL194
Circuit 2 - Suction temperature probe alarm
Automatic reset
Disconnecting
circuit 2
DI1118
AL195
Circuit 2 - Fluid temperature probe alarm
Automatic reset
Message only
DI1119
AL196
Circuit 2 Envelope - High compression
Automatic reset
Disconnecting
circuit 2
DI1120
AL197
Circumference 2 Envelope -
High discharge pressure
Automatic reset
to: 3 times
within 3600 s
Disconnecting
circuit 2
DI1121
AL198
Circuit 2 Envelope - High motor current
Automatic reset
Disconnecting
circuit 2
DI1122
AL199
Circuit 2 Envelope - High suction pressure
Automatic reset
Disconnecting
circuit 2
DI1123
AL200
Circuit 2 Envelope - Low compression
Automatic reset
Disconnecting
circuit 2
DI1124
AL201
Circuit 2 Envelope - Low differential pressure
Automatic reset
Disconnecting
circuit 2
DI1125
AL202
Circuit 2 Envelope - Low discharge pressure
Automatic reset
Disconnecting
circuit 2
DI1126
AL203
Circuit 2 Envelope - Low suction pressure
Automatic reset
Disconnecting
circuit 2
DI1127
AL204
Circuit 2 Envelope - High
discharge temperature
Automatic reset
Disconnecting
circuit 2
DI1128
AL205
Circuit 2 Expansion valve - Low overheating
Automatic reset
to: 3 times
within 3600 s
Disconnecting
circuit 2
DI1129
AL206
Circuit 2 Expansion valve - Low
evaporation pressure
Automatic reset
Disconnecting
circuit 2
DI1130
AL207
Circuit 2 Expansion valve - High
evaporation pressure
Automatic reset
Disconnecting
circuit 2
DI1131
AL208
Circuit 2 Expansion valve - High
condensation temperature
Automatic reset
Disconnecting
circuit 2
DI1132
AL209
Circuit 2 Expansion valve - Low
suction temperature
Automatic reset
Disconnecting
circuit 2
DI1133
AL210
Circuit 2 Expansion valve - Motor error
Automatic reset
Disconnecting
circuit 2
DI1134
AL211
Circuit 2 Expansion valve -
Emergency shutdown
Automatic reset
Disconnecting
circuit 2
DI1135
AL212
Circuit 2 Expansion valve - Set out of range
Automatic reset
Disconnecting
circuit 2
DI1136
AL213
Circuit 2 Expansion valve - Settings range error Automatic reset
Message only
DI1137
AL214
Circuit 2 Expansion valve - Offline
Automatic reset
Disconnecting
circuit 2
DI1138
Содержание ZHHS-01-10K-R290-V5-M
Страница 2: ......
Страница 69: ...JBG HT v 2 0 69 INSTRUCTION MANUAL HEAT PUMP...