– HEAT PUMP
4.2. Location of the pump in relations to noise emission
The comfort of an air heat pump, both for the owner and the close environment, comes down to the noise emis-
sions during its operation. In the case of an air heat pump, the operation of the fans has a significant impact on
sound emissions, which directly determines the location of the outdoor unit. Sound emission values are deter-
mined outside the building, at a distance of 0.5 m from the center of an open window.
4.3. Transportation
It is imperative that the heat pump be transported individually and in an upright position as marked on the
package. It is absolutely forbidden to tilt the heat pump more than 45°. The heat pump can be transported using
a transport cart or by hand. When transporting, take special care not to damage the unit. Due to the sharp edges
present, persons performing transportation are required to use protective gloves. Upon delivery to the instal-
lation site, check the model name and serial number of the units. The unit must always be stored in an upright
position and be protected from moving. Failure to comply with the above recommendation will result in
loss of
warranty.
4.4. Unpacking the product
Before unpacking the device, carry out a visual inspection to check for any damage to the transport packaging.
Particular attention should be paid to cracks and bulges in the box. The main activity after unloading the equip-
ment, is to check whether the equipment was not damaged during transport. If a defect is detected, a damage
report should be written in the presence of the driver with its confirmation on the document. Any damage noticed
during the unpacking of equipment should be immediately reported to the transport company and the service
department.
4.5. Storage
Unit should be stored in its original packaging, at temperatures between -35°C and 50°C and protected from
corrosive weather conditions.
4.6. Mechanical installation and mounting
1 )
When installing a heat pump, it is imperative to use protective equipment and personal pro-
tective clothing!
2 ) The heat pump must be installed with vibration-damping rubber dampers on a stable and rigid base
that provides adequate strength under the load of the unit.
3 ) In order to ensure proper operation of the heat pump, it should be placed in a place with low dust, pro-
viding the least possible corrosive conditions, which ensures proper air circulation and safe opening
of the unit. The ambient temperature at the installation site should not 43°C.
4 ) The connection to the power grid should be made by an electrician with current electrical licenses.
4.6.1.
Setting up the outdoor unit – general guidelines
1 ) In order to ensure adequate airflow to the outdoor unit, it is recommended to install it in an open space.
2 ) The unit must be installed in a way that prevents recirculation of outside air.
3 ) It is not recommended to install the unit near the bedroom or living room due to the generated noise.
4 ) The unit should not be installed in an area with flammable, volatile and corrosive substances.
5 ) The outdoor unit absolutely must have an adequate drainage system.