62
© JBG-HT (v.2.0)
INSTRUCTION MANUAL
– HEAT PUMP
Code
Description
Type
Result
Modbus
AL145
Circuit 1 Inverter - STO error detection (23)
Automatic reset
Power + circuit
1 shutdown
DI1087
AL146
Circuit 1 Inverter - STO error detection (24)
Automatic reset
Power + circuit
1 shutdown
DI1088
AL147
Circuit 1 Inverter - Grounding error (25)
Automatic reset
Power + circuit
1 shutdown
DI1089
AL148
Circuit 1 Inverter - ADC conver-
sion synchronization error (26)
Automatic reset
Power + circuit
1 shutdown
DI1090
AL149
Circuit 1 Inverter - Hardware syn-
chronization error (27)
Automatic reset
Power + circuit
1 shutdown
DI1091
AL150
Circuit 1 Inverter - Drive overload (28)
Automatic reset
Power + circuit
1 shutdown
DI1092
AL151
Circuit 1 Inverter - Error code (29)
Automatic reset
Power + circuit
1 shutdown
DI1093
AL152
Circuit 1 Inverter - Unexpected reboot (98)
Automatic reset
Power + circuit
1 shutdown
DI1094
AL153
Circuit 1 Inverter - Unexpected stop (99)
Automatic reset
Power + circuit
1 shutdown
DI1095
AL154
Circuit 1 Compressor - Start-up error
User reset
Power + circuit
1 shutdown
DI1096
AL155
Circuit 1 Compressor - Pressure differen-
tial greater than allowed during startup
Automatic reset
Power + circuit
1 shutdown
DI1097
AL159
Circuit 1 - User alarm freezing
evaporation temperature
Automatic reset
to: 3 times
within 3600 s
Disconnect-
ing circuit 1
DI1101
AL160
Circuit 1 - Compressor Maintenance 1
Automatic reset
Only message
DI1102
AL161
Circuit 1 - Compressor maintenance 2
Automatic reset
Only message
DI1103
AL162
Circuit 1 - Condensation tem-
perature probe alarm
Automatic reset
Disconnect-
ing circuit 1
DI1104
AL163
Circuit 1 - Fan 1 circuit 1 maintenance
Automatic reset
Only message
DI1105
AL164
Circuit 1 - Fan 2 circuit 1 maintenance
Automatic reset
Only message
DI1106
AL165
Circuit 1 - Fan 3 circuit 1 maintenance
Automatic reset
Only message
DI1107
AL166
Circuit 1 - High pressure alarm
from pressure switch
Automatic reset
to: 3 times
within 3600 s
Disconnect-
ing circuit 1
DI1108
AL167
Circuit 1 - Low pressure alarm
from pressure switch
Automatic reset
to: 3 times
within 3600 s
Disconnect-
ing circuit 1
DI1109
AL168
Circuit 1 – Compressor 1 overload
Automatic reset
to: 3 times
within 3600 s
Compressor
shutdown
1 circuit 1
DI1110
AL169
Circuit 1 – Compressor 2 overload
User reset
Compressor
shutdown
1 circuit 1
DI1111
AL170
Circuit 1 - Completion of pumping
for maximum time
Automatic reset
Only message
DI1112
AL171
Circuit 1 - Evaporation freezing
temperature source alarm
Automatic reset
to: 3 times
within 3600 s
Disconnect-
ing circuit 1
DI1113