26
© JBG-HT (v.2.0)
INSTRUCTION MANUAL
– HEAT PUMP
6 ) It is recommended to install the device with an eave or the use of a special canopy to protect the
supply and cooling pipes from rupture caused by precipitation, such as falling snow.
7 ) Due to the run-off condensate, it is not recommended to install the device over the sidewalk or other
traffic rows, where a risk of icing can occur.
8 )
The minimum distances between the device and other partitions must be strictly adhered to.
The unit is not suitable for the installation in areas, where a water spray may be used.
4.6.1.1.
Ground mounting guidelines
1 ) Prepare the foundation in accordance with local conditions:
•
dig a hole in the ground,
•
insert draining pipe for the condensate drainage (10K fi100, for 15K fi160),
•
pile up a layer of coarse gravel.
2 ) Construct two foundation footings.
3 ) Make a gravel base between the foundation footings.
4 ) Level the unit at all points.
Required mounting distances of the pump on the ground:
MINIMAL
DISTANCE
VALUE [mm]
A
400
B
600
C
1000
D
1000
E
1000
F
300
Tab. 11. Minimal recommended distance for ground mounting.
Fig. 20. Layout of the heat pump outdoor
unit for ground mounting.
In order to set the outdoor unit on the ground, use:
a) Rubber feet (included), rubber base optional