© JBG-HT (v.2.0)
61
INSTRUCTION MANUAL
– HEAT PUMP
Code
Description
Type
Result
Modbus
AL121
Circuit 1 Expansion valve - Configuration error
Automatic reset
Disconnect-
ing circuit 1
DI1063
AL122
Circuit 1 Inverter - Offline
Automatic reset
Power + circuit
1 shutdown
DI1064
AL123
Circuit 1 Inverter - Drive current overload (01)
Automatic reset
Power + circuit
1 shutdown
DI1065
AL124
Circuit 1 Inverter - Motor overload (02)
Automatic reset
Power + circuit
1 shutdown
DI1066
AL125
Circuit 1 Inverter - DC bus voltage overload (03) Automatic reset
Power + circuit
1 shutdown
DI1067
AL126
Circuit 1 Inverter - DC bus
voltage underload (04)
Automatic reset
Power + circuit
1 shutdown
DI1068
AL127
Circuit 1 Inverter - Drive tem-
perature overload (05)
Automatic reset
Power + circuit
1 shutdown
DI1069
AL128
Circuit 1 Inverter - Drive tem-
perature underload (06)
Automatic reset
Power + circuit
1 shutdown
DI1070
AL129
Circuit 1 Inverter - Equipment
current overload (07)
Automatic reset
Power + circuit
1 shutdown
DI1071
AL130
Circuit 1 Inverter - PTC motor tem-
perature overload (08)
Automatic reset
Power + circuit
1 shutdown
DI1072
AL131
Circuit 1 Inverter - IGBT module error (09)
Automatic reset
Power + circuit
1 shutdown
DI1073
AL132
Circuit 1 Inverter - CPU error (10)
Automatic reset
Power + circuit
1 shutdown
DI1074
AL133
Circuit 1 Inverter - Default parameters (11)
Automatic reset
Power + circuit
1 shutdown
DI1075
AL134
Circuit 1 Inverter - DC bus ripple (12)
Automatic reset
Power + circuit
1 shutdown
DI1076
AL135
Circuit 1 Inverter - Data com-
munication failure (13)
Automatic reset
Power + circuit
1 shutdown
DI1077
AL136
Circuit 1 Inverter - Drive thermistor error (14)
Automatic reset
Power + circuit
1 shutdown
DI1078
AL137
Circuit 1 Inverter - Failure of
automatic tuning (15)
Automatic reset
Power + circuit
1 shutdown
DI1079
AL138
Circuit 1 Inverter - Drive disabled (16)
Automatic reset
Power + circuit
1 shutdown
DI1080
AL139
Circuit 1 Inverter - Motor phase error (17)
Automatic reset
Power + circuit
1 shutdown
DI1081
AL140
Circuit 1 Inverter - Internal fan error (18)
Automatic reset
Power + circuit
1 shutdown
DI1082
AL141
Circuit 1 Inverter - Speed error (19)
Automatic reset
Power + circuit
1 shutdown
DI1083
AL142
Circuit 1 Inverter - PFC module error (20)
Automatic reset
Power + circuit
1 shutdown
DI1084
AL143
Circuit 1 Inverter - PFC voltage overload (21)
Automatic reset
Power + circuit
1 shutdown
DI1085
AL144
Circuit 1 Inverter - PFC voltage underload (22)
Automatic reset
Power + circuit
1 shutdown
DI1086
Содержание ZHHS-01-10K-R290-V5-M
Страница 2: ......
Страница 69: ...JBG HT v 2 0 69 INSTRUCTION MANUAL HEAT PUMP...