© JBG-HT (v.2.0)
35
INSTRUCTION MANUAL
– HEAT PUMP
5 ) Drainage of condensed water must be provided by a pipe with a minimum diameter of 100 mm for 10K
and 160 mm for 15K. It is permissible to use a drain inserted vertically into the ground for a minimum of
90 cm, if the ground is permeable to water.
6 ) Pipe dimensions:
Dimensions of CH piping
Heat pump
Copper
pipes
Steel pipes
Polypropyl-
ene pipes
Max. flow
Min. flow
ZHHS-01-10K-R290-V5
28 x 1
32 (5/4’’)
32 x 4,4
1,68 m
3
/h
0,54 m
3
/h
ZHHS-01-15K-R290-V5
35 x 1,5
32 (5/4’’)
40 x 5,5
2,1 m
3
/h
0,72 m
3
/h
Tab. 14. CH pipe dimensions
8 ) A CH buffer is recommended in thermally upgraded facilities.
9 ) Recommended methods against freezing:
A. Use propylene antifreeze throughout the system to -7°C. Increase the flow rate by 10% on the
circulation pump. Glycol concentration must not exceed 35%.
B. Use of a system with manual removal of water from the exchanger. Two drain valves in the form
of shut-off valves should be installed in the building to remove water from the exchanger by gravity.
Additional two shut-offs to prevent the removal of water from the rest of the system.
Fig. 27. Antifreeze protection.