INSTRUCTION MANUAL
– HEAT PUMP
7.3. Disassembly and disposal
1 ) Be particularly careful when proceeding to disassemble the heat pump or its electrical components
and subassemblies.
2 ) Disconnect the heat pump from the power supply before disassembling the unit.
3 ) After disconnecting the power supply, wait 90 seconds before opening the unit. Voltage may remain
on the frequency converter during this time.
4 ) After disconnecting the pump from the power supply, the refrigerant should be released from the
system in the open air.
5 ) Only persons familiar with the handling of R290 refrigerant may perform the task.
6 ) Use personal protective equipment and carry fire extinguishers.
7.4. Decommissioning the appliance
The decommissioning of electrical and electronic appliances should be conducted in accordance with the
current national law in which the appliance was being used.
7.5. Error codes
Code
Description
Type
Result
Modbus
AL000
Unit - Prototype alert
Automatic reset
Unit shutdown
DI1000
AL001
Unit - Remote alarm
User reset
Unit shutdown
DI1001
AL002
Unit - Error in the number of
records retained in memory
User reset
Only message
DI1002
AL003
Unit - Error in saving records in memory
User reset
Only message
DI1003
AL004
Unit - User inlet water temperature probe
Automatic reset
Disabling user
adjustment (*1)
DI1004
AL005
Unit - User outlet water temperature probe
Automatic reset
Disabling user
adjustment (*1)
DI1005
AL006
Unit - Source inlet water temperature probe
Automatic reset
Only message
DI1006
AL007
Unit - Outdoor temperature probe
Automatic reset
Only message
DI1007
AL008
Unit - user pump 1 overload
User reset
Disabling user
adjustment
DI1008
AL009
Unit - Source pump 1 overload
User reset
Unit shutdown
DI1009
AL010
Unit - Flow switch alarm - no flow
when user pump 1 is active
Automatic reset
to: 5 times
within 3600 s
Disabling user
adjustment
DI1010
AL011
Unit - Flow switch alarm - no flow
when source pump 1 is active
Automatic reset
to: 5 times
within 3600 s
Unit shutdown
DI1011
AL012
Unit - User pump grounding alarm
User reset
Disabling user
adjustment
DI1012
AL013
Unit - User pump grounding alarm
User reset
Unit shutdown
DI1013
AL014
Unit - User 1 Pump maintenance
Automatic reset
Message only
DI1014
AL015
Unit - Source 1 pump maintenance
Automatic reset
Message only
DI1015