INSTRUCTION MANUAL

 – HEAT PUMP

4.10.4. 

WiFi Configuration

After 

connecting the laptop to the LAN port on Teltonica

, we enter the device through the address we see in 

the address bar (

172.28.29.254

). We log in with the following credentials to the Montera account:

1 )  In order to connect the router to the client’s wireless network, we select 

NETWORK 

then

 Wireless

2 )  Scan the network by selecting

 SCAN.

3 )  From the list of available networks (there may be many in range), select the client’s network by 

choosing 

JOIN NETWORK. 

If there is none, it is possible that none are in range or the antenna has 

not been screwed in. 

Содержание ZHHS-01-10K-R290-V5-M

Страница 1: ...HEAT PUMP JBG 2 SP Z O O RESERVES THE RIGHT TO MAKE CHANGES TO THE PRODUCTS AND INFORMATION CONTAINED IN THE DOCUMENTATION WITHOUT NOTICE ALL RIGHTS RESERVED Translation of the original manual CAUTIO...

Страница 2: ......

Страница 3: ...ump operation in heating mode 11 3 2 2 Pump operation in cooling mode 11 3 2 3 Heat pump operation envelope 12 3 3 Pump design 13 3 3 1 ZHHS 01 10K R290 V5 Pump 13 3 3 2 ZHHS 01 15K R290 V5 Pump 16 3...

Страница 4: ...arting up the heat pump 46 5 1 Controller Main Screen 46 5 2 Menu Icons 47 5 3 Turning on and off 47 5 4 CH and DHW temperature settings 47 5 5 Logging in 48 5 6 Options and settings 48 5 6 1 CH DHW C...

Страница 5: ...electronic Heating DHW Minimum working pressure bar 1 0 Maximum working pressure bar 3 0 Rated flow m h 1 17 1 48 External operating temperature range C from 20 to 35 Feed water temperature C from 20...

Страница 6: ...supplied to drive the compressor solar heat accumulated in the ground heat or air central heating system electrical energy 230 V or 380 V Qd QB L Fig 1 Principle of operation of a heat pump In heat p...

Страница 7: ...nsport the device must not be connected to the mains electric ity contact service 7 Use the device in accordance with the purpose for which it was designed 8 Before connecting the device check the cor...

Страница 8: ...hich are life threatening in case of direct contact Any work in the vicinity of the electrical board must be carried out only by qualified and authorized personnel with the appropriate professional au...

Страница 9: ...must be grounded The device should be kept away from environments that are flammable or corrosive A dedicated electrical connection should be used to power the device otherwise failure may occur Do no...

Страница 10: ...id interference with the operation of the product the electrical supply should be within the speci fied limits 3 phase 400 V 10 50 Hz 2 9 Risk of environmental contamination from leaking refrigerant T...

Страница 11: ...n forced exchanger 2 The refrigerant in the evaporator evaporates and returns in the gas fraction to the compressor The indoor installation is equipped with a three way valve 3 WAY which distributes t...

Страница 12: ...ircuit 0 55 kg 0 8 kg Tab 3 Dedicated amount of refrigerant 3 2 2 Heat pump operation envelope The heat pump is able to operate under certain conditions Approaching the limits may cause it to go outsi...

Страница 13: ...ydrator filter 2 Compressor inverter 12 LP Pressure transmitter 3 Choke coil 13 HP Pressure transmitter 4 Evaporator 14 HP Pressure switch 5 Fan 15 LP Service port 6 Fan support 16 HP Service port 7 F...

Страница 14: ...icture of the heat pump rear view 3 3 1 1 External dimensions Front view Side view Fig 5 External dimensions of the heat pump front view Fig 6 External dimensions of the heat pump side view Rear view...

Страница 15: ...filter 2 Compressor inverter 12 LP Pressure transmitter 3 Choke coil 13 HP Pressure transmitter 4 Evaporator 14 HP Pressure switch 5 Fan 15 LP Service port 6 Fan support 16 HP Service port 7 Fan mesh...

Страница 16: ...Rear view Photo 3 Picture of the heat pump front view Photo 4 Picture of the heat pump rear view 3 3 2 1 External dimensions Front view Side view Fig 10 External dimensions of the heat pump front vie...

Страница 17: ...JBG HT v 2 0 17 INSTRUCTION MANUAL HEAT PUMP Rear view Fig 12 External dimensions of the heat pump rear view Bottom view Fig 13 External dimensions of the heat pump bottom view...

Страница 18: ...oller case 3 Control board 4 pGDX display screen 5 pGDX display screen frame 6 Contactor 7 24V power supply Fig 14 Design of heat pump indoor unit Tab 6 Description of marked parts of the heat pump in...

Страница 19: ...JBG HT v 2 0 19 INSTRUCTION MANUAL HEAT PUMP 3 3 4 Indoor unit Hydrobox Option 2 Fig 16 Diagram of the hydraulic module...

Страница 20: ...13 DHW return 5 pGDX screen display frame 14 CH power supply 6 pGDX screen display 15 DHW power supply 7 Diaphragm vessel 16 CH return 8 3 way valve 17 HP return 9 Pressure gauge safety bar 18 HP fee...

Страница 21: ...JBG HT v 2 0 21 INSTRUCTION MANUAL HEAT PUMP 3 3 5 Indoor unit Hydrotower Option 3 Fig 18 Diagram of the hydraulic tower...

Страница 22: ...agm vessel 16 CH power supply 6 Electric heater 17 CH return 7 Safety thermal switch 18 HP Return 8 Automated vent 19 DHW power supply 9 3 way valve 20 DHW circulation 10 Controller 21 Cold domestic w...

Страница 23: ...uency inverter Brushless fan PWM pump Picture Component name Controller Plate heat exchanger Lamellar evaporator Flow meter Tab 9 Standard components used in the heat pump 3 5 Accessories Picture Comp...

Страница 24: ...ust be provided Do not install the product on wooden framed buildings and lightweight roofs Installation on a sloping roof is not allowed 9 The air temperature at the outlet is about 5 C lower than th...

Страница 25: ...er the equipment was not damaged during transport If a defect is detected a damage report should be written in the presence of the driver with its confirmation on the document Any damage noticed durin...

Страница 26: ...areas where a water spray may be used 4 6 1 1 Ground mounting guidelines 1 Prepare the foundation in accordance with local conditions dig a hole in the ground insert draining pipe for the condensate d...

Страница 27: ...onnecting the outdoor unit to the indoor unit 1 After mounting the outdoor and indoor units look for the nearest place in the wall to make a hole It is recommended that the hole be char acterized by t...

Страница 28: ...installation 4 8 1 Requirements The device is designed to be powered from the electricity grid 1 Power supply cables and power circuit protection should be selected to meet the condition of auto mati...

Страница 29: ...After connecting the device to the power grid take appropriate electrical measurements and draw up a measurement protocol 19 Control wires and sensors should be routed at a distance of min 100 mm fro...

Страница 30: ...le PE1 x 2 5 mm2 Circulation pump power supply 3 x 1 mm2 PWM control 2 x 0 25 mm2 Flowmeter 2 x 0 25 mm2 NTC probe 3s 2 x 0 25 mm2 Communication cable service 2 x 0 25 mm2 PGDe display power cable 6 x...

Страница 31: ...HT v 2 0 31 INSTRUCTION MANUAL HEAT PUMP 4 8 2 Diagrams of the electrical system 4 8 2 1 Diagram of the 3 phase electrical system in the outdoor unit Fig 23 Diagram of electrical system of the outdoor...

Страница 32: ...32 JBG HT v 2 0 INSTRUCTION MANUAL HEAT PUMP 4 8 2 2 Diagram of the electrical system of the 3 phase indoor unit Fig 24 Diagram of the electrical system of the indoor unit...

Страница 33: ...2 T3 NO A2 A1 2 x 0 5 mm2 Screen display LAN Heat pump ext unit control B1 Return temperature sensor B2 B3 Plant temperature sensor in buffer B4 External temperature sensor NO1 3 way valve DHW flow NO...

Страница 34: ...eatingcircuitmustbethermallyinsulated TheinsulationmustberesistanttoUVaswell as high and low air temperatures 2 Connect the water return and supply of the heat pump as presented in Fig 26 Fig 26 Heat...

Страница 35: ...0 54 m3 h ZHHS 01 15K R290 V5 35 x 1 5 32 5 4 40 x 5 5 2 1 m3 h 0 72 m3 h Tab 14 CH pipe dimensions 8 A CH buffer is recommended in thermally upgraded facilities 9 Recommended methods against freezin...

Страница 36: ...n valve 14 Mesh filter Magnetic separator 15 Pressure relief valve 17 Proportional relief valve Tab 15 Description of marked parts in hydraulic system diagrams 4 9 2 1 Diagram of hydraulic system with...

Страница 37: ...es buffer underfloor heating 4 9 2 3 Diagram of hydraulic system without a buffer underfloor heating 25 12 A B M 1 5 2 14 7 15 10 10 15 10 11 7 13 10 14 12 17 8 15 7 6 3 Fig 30 Diagram of hydraulic sy...

Страница 38: ...em hydrobox option with a combination tank 25 12 M M 14 7 15 16 10 10 1 5 2 8 6 12 7 11 7 13 10 10 10 10 10 14 3 4 Fig 32 Diagram of hydraulic system with a combination tank mixed heating Plant centra...

Страница 39: ...NOWE 6 5 1 2 13 4 3 12 11 10 9 8 Fig 33 Hydrobox hydraulic diagram 4 9 2 7 Detailed diagram of Hydrotower module 1 200L DHW Tank 2 Diaphragm vessel 3 Electric heater 4 Safety thermic 5 3 way valve 6 M...

Страница 40: ...ating system Visually check the water for precipitation of other materials If this occurs the user is required to clean the system Use only demineralized heating water or water that complies with the...

Страница 41: ...he tank inserting it inside the tank through the designated entrance The location of the sensor is presented in Figure 36 1 Tank 2 Coli 3 Cold water 4 DHW supply 5 temperature sensor 6 DHW circulation...

Страница 42: ...4 10 Installing the Internet module 4 10 1 WiFi connection at the User s site Wireless network as an output to the Internet WAN Port Internet WiFi as WAN LAN Port Pump router Client router 4 10 2 Cabl...

Страница 43: ...e log in with the following credentials to the Montera account 1 In order to connect the router to the client s wireless network we select NETWORK then Wireless 2 Scan the network by selecting SCAN 3...

Страница 44: ...previous steps by selecting SAVE APPLY 6 After the page refreshes itself the wireless network status screen will appear We can see the correct Running status and the percentage of signal quality here...

Страница 45: ...hutdown mode pump off defrost standby mode 1 outdoor temperature 4 current date and time 6 active calendar 2 DHW temperature 5 heat pump status mode 7 installation operation mode 3 CH temperature 5 2...

Страница 46: ...off 5 4 CH and DHW temperature settings CH operation point Measured value DHW operation point Measured value Settings should be made for the various available modes of operation 5 5 Logging in Access...

Страница 47: ...Calendar Calendar activation 5 6 2 Calendar Operation modes of the installation during schedule activity Inactive Comfort Off Boost Economic 5 6 3 Setting a schedule The working day of the unit can b...

Страница 48: ...ented in the form of colored bars that show the mode set Activities are according to the colors of the mode icons on the right Clicking on the bar of each day takes you to the day settings 5 6 6 Speci...

Страница 49: ...allows you to set the basic parameters of heat pump operation At any time the user will be able to return to this procedure to change the settings he or she previously selected To start the Quick Gui...

Страница 50: ...nsor that will be the master sensor in the control algorithms Before starting the heat pump the system must be filled and vented If these actions are not performed the controller will not allow you to...

Страница 51: ...sensor the compressor regulates For users with a buffer it is recommended to set the regulation after the temperature of the water in the buffer Otherwise the Inlet Outlet type of regulation should b...

Страница 52: ...For this purpose a pre heating procedure has been created which allows you to heat the water in the CH and DHW circuit to the set temperature with an electric heater It is necessary to set the ambient...

Страница 53: ...hat point For ambient temperatures between the designated points the setpoint is calculated by interpolation The exceptions are the limit points X1 and X4 beyond which the setpoint no longer changes T...

Страница 54: ...er has Depending on your choice the appro priate windows will be displayed later The next step is to configure the CH buffer pump if any This is the circulating pump after the buffer that unloads the...

Страница 55: ...ith three heating circuits is selected then instead of the regulated pump of the second circuit the control output is used for another mixing valve and analogous variables are set for the valve of the...

Страница 56: ...s the radiator supply temperature Maintaining the correct temperature of the underfloor supply is ensured by the mixing system accessory which mixes the outlet water from the exchanger with a higher t...

Страница 57: ...ventilated Clean the air side heat exchangers of dust and lingering leaves regularly with a vacuum cleaner This will maintain good heat exchange It is abso lutely forbidden to wash the exchanger with...

Страница 58: ...utdown DI1001 AL002 Unit Error in the number of records retained in memory User reset Only message DI1002 AL003 Unit Error in saving records in memory User reset Only message DI1003 AL004 Unit User in...

Страница 59: ...s Disabling DHW control DI1026 AL027 Unit DHW pump 1 overload User reset Disabling DHW control DI1027 AL028 Unit Outdoor coil temperature probe Automatic reset Message only DI1028 AL029 Unit User anti...

Страница 60: ...1 Expansion valve Low overheating Automatic reset to 3 times within 3600 s Disconnect ing circuit 1 DI1049 AL108 Circuit 1 Expansion valve Low evaporation pressure Automatic reset Disconnect ing circ...

Страница 61: ...BT module error 09 Automatic reset Power circuit 1 shutdown DI1073 AL132 Circuit 1 Inverter CPU error 10 Automatic reset Power circuit 1 shutdown DI1074 AL133 Circuit 1 Inverter Default parameters 11...

Страница 62: ...ircuit 1 shutdown DI1097 AL159 Circuit 1 User alarm freezing evaporation temperature Automatic reset to 3 times within 3600 s Disconnect ing circuit 1 DI1101 AL160 Circuit 1 Compressor Maintenance 1 A...

Страница 63: ...erential pressure Automatic reset Disconnecting circuit 2 DI1125 AL202 Circuit 2 Envelope Low discharge pressure Automatic reset Disconnecting circuit 2 DI1126 AL203 Circuit 2 Envelope Low suction pre...

Страница 64: ...ter DC bus voltage underload 04 Automatic reset Power circuit 2 shutdown DI1148 AL225 Circuit 2 Inverter Drive tem perature overload 05 Automatic reset Shutdown of power circuit 2 DI1149 AL226 Circuit...

Страница 65: ...s to the building structure YES Outdoor Unit Protective Area Dimension of the protective area in accordance with the requirements of the installation instructions YES No openings in the building windo...

Страница 66: ...the return of the heating system YES Installed magneto demulsifier on the return of the heating system YES The minimum water charge necessary for proper operation and defrosting of the outdoor unit is...

Страница 67: ...ording to the instructions YES Control wires and sensors routed at a distance of min 100mm from power wires YES Correct 3 phase power cable used min 5x2 5mm2 5x4mm2 The correct overcurrent circuit bre...

Страница 68: ...Additional heat source none dry contact integrated heater Bivalent point C H C DHW bivalent point C Handover to User Heat pump operation instruction YES Safety instructions on R290 refrigerant YES Fun...

Страница 69: ...JBG HT v 2 0 69 INSTRUCTION MANUAL HEAT PUMP...

Страница 70: ...y Produkcja Factory Sekretariat Secretariat 43 254 Warszowice ul Gajowa 5 Poland 43 240 ory al Jana Paw a II 46 Poland 48 32 494 00 00 info jbg2 com PRODUCER OF PROFESSIONAL REFRIGERATION EQUIPMENT PR...

Отзывы: