12.5 Procedure.
1.
The transmitter must be placed on its charger, the wired emergency stop must be unlocked and the gate must
be closed or the safety light barrier activated.
This state is indicated by the white "V2" led and static output 58 which are off.
2.
Before entering the protected area, the operator picks up the transmitter from the charger. The charger contact
(S31-
S32) opens. The operator has a certain period of time (set by the “A” switches on the receiver) to activate the
transmitter.
The activation waiting tim
e is indicated by rapid flashing of the white “V2” led and static output 58.
3.
Wait until the transmitter orange indicator light goes off before activating the transmitter
with green “On” button.
Once activated
, the white “V2” led and static output 58 come on steady.
4.
In order to pass through the protected access, the operator must simultaneously press the green ON button on
the transmitter and the passage request button located outside the protected area. When the two buttons are
released, the passage is inhibited. This state is indicated by a
Led “V2” and static output 58 which flash slowly. The
operator must move through the gate and close it or go through the safety light barrier before the end of the inhibit
time which is realized by the blinking of the V2 indictor light and the output nb 58. This inhibit time is customizable
by A selector.
5.
This inhibit time is interrupted when the operator crossed the safety light barrier or closed the access zone gate.
White indicator light “V2” and static output 58 are again on steady.
6.
Once the intervention is completed, in order to come out of the area, the operator must again perform the
passage request by simultaneously pressing the On button on the remote control and the passage request button
located inside the equipment. Once the two buttons are released, the passage is again inhibited (slowly flashing
“V2” led and static output 58).
7.
Once outside the protected area, the operator sets the remote control on the charger and the charger contact
clo
ses. The transmitter should be deactivated within 1 second. On deactivation of the remote control, the white “V2”
led and static output 58 go off.
Note:
The inhibit time and the maximum time tolerated between the moment the transmitter is picked up off the
charger and activation of the transmitter can be adjusted using the rotary “A” switches on the receiver.
The two passage request buttons are connected in parallel across terminals S33-S34 of the safety receiver.
As indicated in section
7.3.1
“Special case – Equipment area access”,
an indicator light column should be wired
on the housing containing the safety receiver. Refer to the section covering
7.3
”Receiver and charger
installation precautions.
12.6 Area access in manual mode
The procedure for access is the same, except that the equipment is stopped before the intervention using the
portable transmitter. See section
5.2
“Intervention conditions”.
Here below a sheet to be stuck up next to the indicator light column.
This sheet specifies the states of the equipment and the portable transmitter.