A functional test (automatic or manual) to detect failures shall be performed within the
following test intervals:
at least
every month
for PL e with Category 3 or Category 4 (according to EN ISO
13849-1) [or SIL 3 with HFT (hardware fault tolerance) = 1 (according to EN 62061)];
at least
every 12 months
for PL d with Category 3 (according to EN ISO 13849-1) [or
SIL 2 with HFT (hardware
fault tolerance) = 1 (according to EN 62061)].“
Important :
As installer or manufacturer of the machine, you are also required to indicate these
guidelines for safe use in your own user manual.
Caution :
This manual describes the functions of the RSRA / A002 receivers with a software
version PN5910_BI_A_01_0F_01_03 or higher. Operating modes 8 and 9
(§ 6.2.2
«Control of machine with area access control»)
have been modified with respect to
the previous versions of the RSRA modules.
The modules having this new function carry the type designation « RSRA / A002 »
engraved on the side of the housing. The software version is glued to the back of the
housing.