6.2.3 Diagram of functions according to program selected
Reminder : The program is selected using the 2 « B » switches see
§ 3.4.1
“Choice of receiver (RSRA)
program
”.
Switch B = 8: Access to protected area
Protection circuits connected across S12-S14 and S22-S24 always active if charger contact connected
across S31 and S32 is closed.
Manual startup only by «ON» button connected to S42 following an area access request.
Transmitter acknowledged if charger contact across S31 and S32 is open.
Time-delayed inhibit of safety element connected to S22-S24.
Manual startup by «ON» button of remote control is possible.
tmax.: maximum time for enable of remote control after it has been picked up from charger and maximum time for
inhibiting protection.