[Buraya yazın]
O.
MODBUS
–
RTU SETTINGS
SESESETTINGSI
Enter to Sevice Menu as it is described above (I. Entering To Service Menu)
•
For Modbus ID’s go to parameter 111 . Go to Modbus ID by using
UP
and
DOWN
buttons Set and confirm
by using Mode/Ok
For Modbus Baudrate go to parameter 112 and change Modbus Baudrate by using
UP
and
DOWN
buttons . Set and
confirm by using Mode/Ok
0: 1200 Bps
1: 2400 Bps
2: 4800 Bps
3: 9600 Bps
4: 19200 Bps
5: 38400 Bps
6: 57600 Bps
Note1: All Modbus parameters are Holding register.
Note2: All Modbus parameters are Signed Integer16.
P.
MODBUS REGISTER LIST
PLC Register
Parameters for Controlling the Unit
4001
0
Unit On/Off
0...1
0: Unit On 1: Unit Off
4002
1
Unit Set Temperature
0...999
280 value means 28 ºC
4003
2
Conditioning Mode
0...4
0: Manual Heating
1: Manual Cooling
2: Auto Heating
3: Auto Cooling
4: Auto
4004
3
Exhaust Fan Manual Speed Value
0...6
4005
4
Supply Fan Manual Speed Value
0...6
Temperature Parameters
4006
5
Unit Ambient Temperature
-400...999
280 value means 28 ºC
4007
6
Panel Ambient Temperature
-400...999
Temperatıre on the propanel
4008
7
Exhaust air temperature
-400...999
Exhaust air temperature
4009
8
Supply air temperarure
-400...999
If there is no temperature value on
the unit, the value will be shown as
"
32767
4010
9
Outside air temperature
-400...999
4011
10
Water Coil temperature
-400...999
4012
11
Evaporator Temperature
-400...999
4013
12
Condenser Temperature
-400...999
4014
13
Exchanger Temperature
-400...999
Unit Performance Parameters
4015
14
Bms Entry
0...1
0: Unit On 1: UnitOff
4016
15
Boost Entry
0...1
0: Works as prgrammed
1: Fans work in full speed.
4017
16
Exhaust Fan Air Blowing Info
0...1
Info Exhaust Fan
4018
17
Supply Fan Air Blowing Info
0...1
Info for Supply Fan
4019
18
Filter 1 Dirtiness Info
0...1
4020
19
Filter 2 Dirtiness Info
0...1
4021
20
Electrical Heater Safety Thermostat Info
0...1
Safety Thermostate Info