Notes;
The electrical board comes with Scenario Number 4 as default.
To change the scenario please follow the steps defined in
‘’S.Changing the Scenarios’’
When Scenario 5 is selected , unit is ready to work as
Heat Recovery with 1 Step Pre heater 2 Steps After Heater .
Default Values for Pre Heater;
Parameter
Description
Default Value
Detail
152
Pre Heater Hysterises Value
2
ºC
Shows 20 on the screen
153
Pre Heater Step Difference as Temperature
5
ºC
Shows 50 on the screen
160
Pre Heater Set Temperature
5
ºC
Shows 50 on the screen
The connection of the fresh air temperature sensor and the electrical heater should be done to the electrical board.
Below parameters should be set as follows from the service parameters menu. Please follow the instructions
described at
‘’I: Entering to Service Menu’’
to enter Service Menu
Parameter
Description
Value
Detail
154
Pre Heater Step Quantity
1
159
After Heater Step Quantity
2
422
After Heater Relay Selection
2
423
Pre Heater Relay Selection
1