4111
110
Service Setting Password
0...9999
Main card password is "
58"
Building Management Modbus-RTU Parameters
4112
111 Modbus ID
1...254
4113
112 Modbus Baudrate
0...7
Screen Value Registers
4114
113
Show Temperature Value
0...3
0:Do Not Show
1:OutsideTemperature
2:Supplied Air Temperature
3:Show both temperatures
4115
114
Show Analog Inlet
0...3
0:Do not show
1:CO2
2:Air Quality
3:Humidity
Filter Time Counter Parameters
4116
115 Filter Dirtiness Counter
0-9999hour
Counter increases due to working hour
of supply fan
4117
116
Unit Mode Info
0-100
0:Unit Off
1:Damper is opening
2:Fan Starts Working
3:Main Function
4:Valve Closing
5:Fan Stops
6:Frost
7:Defrost
99:Error Mode (Waiting for Reset)
Boost Mode Setting Registers
4118
117 Activate Boost
0-1
0:Deaktive
1:Aktive
Parameters for Temperature Check Point
4119
118
Temperature Check Point
0-3
0:Controller
1:Return Air Temperature
2:Supply Air Teperature
3:Outside Air Temperature
4120
119
Exhaust/Fresh Air Damper Opening Period
0-999sec.
Opens damper and start fans and
other components after waiting for
the period defined here
Auto Mode Fan Setting Parameters
4121
120 Auto Mod Fan Min. Speed
0-6
The minimum speed for fans at
auto mod
4122
121
Full Auto Mod Fan Working Stage
0-1
0: Normal
1: Working Continously
4123
122 Full Auto Mod Exhaust Fan Value
0-100
Working value for Exhaust Fan
4124
123 Full Auto Mod Supply Fan Value
0-100
Working value for Supply Fan
4125
124 Full Performance of the Fans at the start
0-1
Full Performance for the fans or not at
the start
4126
125 Passage time between fan steps
0
—999sec.
Passage time between fan steps
4127
126
Fan Hysteresis Value
0-999
If fans work thermostatically, the
hysteresis value between step
changing..
4128
127 The difference value between the fans
0-999
4129
128 Fan delay time at the start
0-999sec.
Waiting time for the fan to start
4130
129
Fan working time after stop command
0-999sec.
Waiting time for fans to stop after stop
command (Cools electrical heater and
other components after they stop
during the delay time.)
4131
130 Exhaust Fan 0. Step Value
0-100
It is recommended not to work motor ,
at a value of exit voltage under 120 V.
4132
131 Exhaust Fan 1. Step Value
4133
132 Exhaust Fan 2. Step Value
4134
133 Exhaust Fan 3. Step Value
4135
134 Exhaust Fan 4. Step Value