[Buraya yazın]
4136
135 Exhaust Fan 5. Step Value
4137
136 Exhaust Fan 6. Step Value
4138
137 Supply Fan 0. Step Value
0-100
It is recommended not to work motor , at
a value of exit voltage under 120 V.
4139
138 Supply Fan 1. Step Value
4140
139 Supply Fan 2. Step Value
4141
140 Supply Fan 3. Step Value
4142
141 Supply Fan 4. Step Value
4143
142 Supply Fan 5. Step Value
4144
143 Supply Fan 6. Step Value
4145
144
Fire Scenario Selection
0-3
0: Shut down both fans
1: Exh. Fan Full Supp. Fan.Off
2: Exh. Fan Off Supp. Fan.Full
3: Both fans are working
4146
145 Cooling and Heating Hysteresis Value
0-999
Pressure Error Parameters
4147
146 Pressure Error Quantity
0-10 each
For instance, if the value is 5 and
there happens 5 pressure error
,unit shuts down. F the values is 0
then unit will shut down with the
first pressure error.
4148
147
Pressure Error Period
1-30min.
Boost ve Heater Limiting Parameters
4149
148 Maximum working time for boost
0-999min
Boost will close at the end of this period
4150
149 Heater Limiting according to Fan
0-1
Pre Heater Setting Parameters
4151
150 Pre Heater Delay time at Start
1-999 Sec.
4152
151 Pre Heater Delay time at Stop
1-999 Sec.
4153
152 Pre Heater Hysteresis Value
1…100
100 value means 10.0ºC
4154
153 Pre Heater Steps as Temperature
4155
154 Pre Heater Step Quantity
0-3
Last Heater Setting Parameters
4156
155 After Heater Opening Delay Time
1-999 Sn
4157
156 After Heater Stopping Delay Time
1-999 Sn
4158
157
After Heater Hysteresis Value
1…100
100 value means 10.0ºC
4159
158 After Heater Steps as Temperature
4160
159 After Heater Step Quantity
Accessories Setting Parameters
4161
160 Pre Heater Set Temperature
-
400…999
4162
161 ByPass Histeresis Value
1…999
4163
162 Rotary Exchanger Histerezsis Value
1…999
PID Setting Parameters
4164
163 Valve P Value
4165
164 Valve I Value
Compressor Setting Parameters
4166
165 Compressor Starting Time
1…999
Starting and Stopping Time of
Compressor can be set.
4167
166 Compressor Stopping Time
1…999
4168
167
Compressor Histeresis Value
1…100
Compresor Defrost Setting Parameters
4169
168 Fan Step in case of defrost
0...6
4170
169
Min. Temperature Value for defrost
-400...999
Содержание CONTROL KIT 5