background image

[Buraya yazın] 

 

4070 

69 

Proportional ByPass Damper Exit Value 

0...100 

 

4071 

70 

Mixing Damper Exit Value 

0...100 

4072 

71 

VRF Exit Value 

0...100 

Weekly Programming Parameter Registers 

4073 

72 

Sunday Starting Time Hour/Minute 

0...2359 

 

Unit works between starting and stopping 
time. 

 

If starting and stopping times are same, 
unit will work all day. 

 

If starting time is later than stopping time , 
unit will not work. 

4074 

73 

Sunday Stopping Time Hour/Minute 

0...2359 

4075 

74 

Monday Starting Time Hour/Minute 

0...2359 

4076 

75 

Monday Stopping Time Hour/Minute 

0...2359 

4077 

76 

Tuesday Starting Time Hour/Minute 

0...2359 

4078 

77 

Tuesday Stopping Time Hour/Minute 

0...2359 

4079 

78 

Wednesday Starting Time Hour/Minute 

0...2359 

4080 

79 

Wednesday Stopping Time Hour/Minute 

0...2359 

4081 

80 

Thursday Starting Time Hour/Minute 

0...2359 

4082 

81 

Thursday Stopping Time Hour/Minute 

0...2359 

The setting should be done  as 

 

Hour:Minute 

4083 

82 

Friday Starting Time Hour/Minute 

0...2359 

4084 

83 

Friday Stopping Time Hour/Minute 

0...2359 

4085 

84 

Saturday Starting Time Hour/Minute 

0...2359 

4086 

85 

Saturday Starting Time Hour/Minute 

0...2359 

4087 

86 

Day Setting 

1...31 

 

4088 

87 

Month Setting 

1...12 

 

4089 

88 

Year Setting 

0...99 

 

4090 

89 

Hour setting 

0...23 

 

4091 

90 

Minute Setting 

0...59 

 

4092 

91 

Seconds setting 

0...59 

 

4093 

92 

Setting day of the week 

1...7 

1:Sunday 2:Monday 3:Tuesday 
4:Wednesday 5:Thursday 6:Friday 
7:Saturday 

 
 

4094 

 
 

93 

 
 

Instant Weekly Programming Check 

 
 

0...2 

0:No weekly Programming 

4095 

94 

RTC Module 

0...1 

1:Unit Works and it has a  weekly 
programming 

4096 

95 

Error Value 

0...99 

 

4097 

96 

Warning Value 

0...99 

 

Menu Setting Parameters 

4098 

97 

Show Fan Mod Menu 

0...1 

 

 

The menus needs to be shown when the 
unit is on should be selected as 1 

4099 

98 

Show Manual Heating  Menu 

0...1 

4100 

99 

Show Manual Cooling Menu 

0...1 

4101 

100  Show Auto Heating Menu 

0...1 

4102 

101  Show Auto Cooling Menu 

0...1 

4103 

102  Show Full  Auto Menu 

0...1 

KeyLock 

4104 

103   KeyLock 

0...1 

0: Key Lock Active  
1: Key Lock de-Active 

Error Parameters 

4105 

104  Critical Error Info 

0...1 

0:No Error 
1: An Error resulting complete shut down 
of the unit. 

4106 

105  Compressor Error Info 

0...1 

0:No Error at compressor  

1: An Error resulting complete shut 
down of the compressor. 

Set Temperature Parameters 

4107 

106  Set Temoerature Min Value 

0...999 

Value of 280 means 28 ºC 

4108 

107  Set Temperature Max Value 

0...999 

Value of 280 means 28 ºC 

Fan Setting  Parameters 

4109 

108  Fan Quantity 

1...2 

1Single 
2Double 

4110 

109  Fan Step Value 

1...6 

 

Password Parameters 

Содержание CONTROL KIT 5

Страница 1: ...JAKKA CONTROL KIT 5 USER MANUAL ...

Страница 2: ...ust and supply fans Working of the unit in Automatic Manual Modes Heating Cooling Fan Modes Room Temperature Sensor User Friendly Design Minimum ve Maximum Set Temperature Limit Constant HVAC R Images Weekly Programming 1 ROOM THERMOSTATE ...

Страница 3: ... air damper bypass damper heating coil cooling coil and also EC fans Main Features Filter Alarm According to Pre set Time counter Pre set Service Time Pre programmed scenario selection via room thermostate Adjustable Mode selection Auto Heating Auto Cooling Manual Heating Manual Cooling Fan Mode Restart with the last paremeters in case of power shortage Connection to building management system Mod...

Страница 4: ...10A 6 Steps Consumption Max 5VA Connection 1 5mm clips Functional Specs On Off via BMs Embedden temperature sensor to room thermostate Control Of Duct Type Temperature Sensor Fresh Air Damper Bypass Air Damper External Sensor Connection NTC 10K 6 Steps Manuael or Auto Speed Selection for Exhaust and Supply Fans seperately Unit On Off info Weekly Programming Carbondioxide Air Quality Sensor Control...

Страница 5: ...01 by using UP and DOWN buttons then press Mode OK button Set hour minute by pressing UP and DOWN buttons then go on by pressing Mode OK Set day month by pressing UP and DOWN buttons then go on by pressing Mode OK Set year by pressing UP and DOWN buttons then go on by pressing Mode OK Set name of the day by pressing UP and DOWN buttons then go on by pressing Mode OK C CHANGING UNIT MODE The mode c...

Страница 6: ...on the screen will be deleted after 2 seconds Then press any button All buttons will be functional again G HOW TO RESET ALARM CODE If Err 0001 alarm or any other alarm code blinking on screen Press FAN and UP buttons simultaneously H HOW TO RESET FILTER DIRTINESS COUNTER When you got 0001 warning on the screen You can reset it by pressing FAN and Mode OK buttons simultaneously Note You can change ...

Страница 7: ...o Parameter you want to change by using UP and DOWN buttons then press Mode OK button Change the parameter by using UP and DOWN buttons then press Mode OK button Get out of menu by pressing ON OFF button Caution All the changes on the service menu should be done by authorized personnel The damage and problems causing by unauthorized changes on the service menu will be on user s responsibility ...

Страница 8: ...nd DOWN and press Mode OK Note Service menu password is 58 Then go to Parameter 118 by using UP and DOWN buttons then press Mode OK button Change the parameter by using UP and DOWN buttons then press Mode OK button Parameter 118 could be one of below numbers 0 Room thermostate 1 Return Air 2 Supply Air 3 Outside Air Get out of menu by pressing ON OFF button Note Selected sensor should be connected...

Страница 9: ... OK Change the value according to table below by using UP and DOWN and press Mode OK Check out from the menu by using ON OFF button Fan Step Parameters 130 Exhaust Fan 0 Step Value 0 100 131 Exhaust Fan 1 Step Value 132 Exhaust Fan 2 Step Value 133 Exhaust Fan 3 Step Value 134 Exhaust Fan 4 Step Value 135 Exhaust Fan 5 Step Value 136 Exhaust Fan 6 Step Value 137 Supply Fan 0 Step Value 0 100 138 S...

Страница 10: ...Caution If the fans run before damper opens fan motors could be broken M ADDING PRE HEATER You can add preheater by configuring the below parameters When the unit is connected to power supply press UP and DOWN buttons simultaneously Enter service menu password 58 by using UP and DOWN and press Mode OK Go and change to below parameter by using UP and DOWN and press Mode OK Change the value by using...

Страница 11: ...ng FAN and UP buttons simultaneously If there is a broken component replace it with a new one If there is an obstacle at the duct systemi clean it a for a better air flow E 0016 Supply Air Flow Error Check the exhaust fan connection cables filter and ducting If 11lla re fine reset the alarm by pressing FAN and UP buttons simultaneously If there is a broken component replace it with a new one If th...

Страница 12: ... 4004 3 Exhaust Fan Manual Speed Value 0 6 4005 4 Supply Fan Manual Speed Value 0 6 Temperature Parameters 4006 5 Unit Ambient Temperature 400 999 280 value means 28 ºC 4007 6 Panel Ambient Temperature 400 999 Temperatıre on the propanel 4008 7 Exhaust air temperature 400 999 Exhaust air temperature 4009 8 Supply air temperarure 400 999 If there is no temperature value on the unit the value will b...

Страница 13: ...tal Putput Online Registers 4044 43 Fresh Air Suction Damper Motor 0 1 0 Off 1 On 4045 44 ByPass Damper Motor 0 1 0 Off 1 On 4046 45 Heating Cooling Coil Valve Exit 0 1 0 Off 1 On 4047 46 Heating Coil On Off Exit 0 1 0 Off 1 On 4048 47 Cooling Coil On Off Exit 0 1 0 Off 1 On 4049 48 Compressor Exit 0 1 0 Off 1 On 4050 49 Compressor 4 way Valve Exit 0 1 0 Off 1 On 4051 50 Unit Working Info Exit 0 1...

Страница 14: ...88 87 Month Setting 1 12 4089 88 Year Setting 0 99 4090 89 Hour setting 0 23 4091 90 Minute Setting 0 59 4092 91 Seconds setting 0 59 4093 92 Setting day of the week 1 7 1 Sunday 2 Monday 3 Tuesday 4 Wednesday 5 Thursday 6 Friday 7 Saturday 4094 93 Instant Weekly Programming Check 0 2 0 No weekly Programming 4095 94 RTC Module 0 1 1 Unit Works and it has a weekly programming 4096 95 Error Value 0 ...

Страница 15: ...ents after waiting for the period defined here Auto Mode Fan Setting Parameters 4121 120 Auto Mod Fan Min Speed 0 6 The minimum speed for fans at auto mod 4122 121 Full Auto Mod Fan Working Stage 0 1 0 Normal 1 Working Continously 4123 122 Full Auto Mod Exhaust Fan Value 0 100 Working value for Exhaust Fan 4124 123 Full Auto Mod Supply Fan Value 0 100 Working value for Supply Fan 4125 124 Full Per...

Страница 16: ...eriod 4150 149 Heater Limiting according to Fan 0 1 Pre Heater Setting Parameters 4151 150 Pre Heater Delay time at Start 1 999 Sec 4152 151 Pre Heater Delay time at Stop 1 999 Sec 4153 152 Pre Heater Hysteresis Value 1 100 100 value means 10 0ºC 4154 153 Pre Heater Steps as Temperature 4155 154 Pre Heater Step Quantity 0 3 Last Heater Setting Parameters 4156 155 After Heater Opening Delay Time 1 ...

Страница 17: ...Universal Input Check Parameeters 4182 181 Number 1 Universal Inlet 400 999 4183 182 Number 2 Universal Input 400 999 4184 183 Number 3 Universal Input 400 999 4185 184 Number 4 Universal Input 400 999 4186 185 Number 5 Universal Input 400 999 4187 186 Number 6 Universal Input 400 999 4188 187 Number 7 Universal Input 400 999 4189 188 Number 8 Universal Input 400 999 4190 189 Number 9 Universal In...

Страница 18: ...9999 9999 4229 228 Number 8 Analog Input 9999 9999 Analog Output Check Parameters 4232 231 Number 1 Analog Output 9999 9999 4233 232 Number 2 Analog Output 9999 9999 4234 233 Number 3 Analog Output 9999 9999 4235 234 Number 4 Analog Output 9999 9999 4236 235 Number 5 Analog Output 9999 9999 4237 236 Number 6 Analog Output 9999 9999 4238 237 Number 7 Analog Output 9999 9999 4239 238 Number 8 Analog...

Страница 19: ... 279 Uın19 Input On Off Selection Universal Digital Input Signal Detecting Delay Setting Parameters 4282 281 Uın1 Input Signal Detecting Delay 0 999 4283 282 Uın2 Input Signal Detecting Delay 4284 283 Uın3 Input Signal Detecting Delay 4285 284 Uın4 Input Signal Detecting Delay 4286 285 Uın5 Input Signal Detecting Delay 4287 286 Uın6 Input Signal Detecting Delay 4288 287 Uın7 Input Signal Detecting...

Страница 20: ...lue 9999 9999 4333 332 Analog Input 2 Maximum Value 9999 9999 4334 333 Analog Input 3 Maximum Value 9999 9999 4335 334 Analog Input 4 Maximum Value 9999 9999 4336 335 Analog Input 5 Maximum Value 9999 9999 4337 336 Analog Input 6 Maximum Value 9999 9999 4338 337 Analog Input 7 Maximum Value 9999 9999 4339 338 Analog Input 8 Maximum Value 9999 9999 4340 339 Analog Input 9 Maximum Value 9999 9999 An...

Страница 21: ...nal Detecting Delay 2 Supply Air Temperature 4405 404 UI 4 Input Signal Detecting Delay 3 Fresh Air Temperature 4406 405 UI 5 Input Signal Detecting Delay 4 Water Coil Temperature 4407 406 UI 6 Input Signal Detecting Delay 5 Evaporator Temperature 4408 407 UI 7 Input Signal Detecting Delay 6 Condensor Temperature 4409 408 UI 8 Input Signal Detecting Delay 7 Exchanger Temperature 4410 409 UI 9 Inpu...

Страница 22: ...ing Valve On Off Exit Number 4433 432 Cooling Heating Valve On Off Exit Number 4434 433 Compressor Exit Number 4435 434 Compressor 4 Way Valve Exit Number 4436 435 Unit On Exit Number 4437 436 Unit in Error Mode Exit Number 4438 437 VRF On Off Exit Number 4439 438 VRF Heating Exit Number 4440 439 VRF Cooling Soğutma Exit Number 4441 440 Humidifier Exit Number 4442 441 Warning Exit Number Analog Ou...

Страница 23: ...ery with Dx Coil VRF 13 Heat Recovery with On Off Valved Water coil 4Pipe 14 Heat Recovery with EC Fan and 3 Steps Electrical Heater 15 Heat Recovery with EC Fan and On Off Valved Water Coil 2Pipe 16 Heat Recovery with EC Fan and On Off Valved Water Coil 4Pipe To change the scenario When the unit is connected to power supply press UP and DOWN buttons simultaneously Enter service menu password 58 b...

Страница 24: ...he electrical board comes with Scenario Number 4 as default To change the scenario please follow the steps defined in Changing the Scenario When Scenario 2 is selected unit is ready to work as Heat Recovery with 3 Steps Electrical Heater With Fresh Air Damper In this mode exhaust and supply fans and after heater can be controlled Temperature is measured by room thermostate If room temperature is m...

Страница 25: ...Heater With By Pass Damper Heat Recovery with 1 Step Pre Heater 2 Steps After Heater mode Works according to set temepareture and control exhaust ans supply fans and after heater Pre heater works according to fresh air sensor Inside air temperature is measured by room thermostate If room temperature is measured below set value temperature will be increased by using after heater If room temperature...

Страница 26: ... screen 153 Pre Heater Step Difference as Temperature 5 ºC Shows 50 on the screen 160 Pre Heater Set Temperature 5 ºC Shows 50 on the screen The connection of the fresh air temperature sensor and the electrical heater should be done to the electrical board Below parameters should be set as follows from the service parameters menu Please follow the instructions described at I Entering to Service Me...

Страница 27: ... please follow the steps defined in S Changing the Scenarios Default Values for Pre Heater Parameter Description Default Value Detail 152 Pre Heater Hysterises Value 2 ºC Shows 20 on the screen 153 Pre Heater Step Difference as Temperature 5 ºC Shows 50 on the screen 160 Pre Heater Set Temperature 5 ºC Shows 50 on the screen When Scenario 6 is selected unit is ready to work as Heat Recovery with 2...

Страница 28: ...ows 20 on the screen 153 Pre Heater Step Difference as Temperature 5 ºC Shows 50 on the screen 160 Pre Heater Set Temperature 5 ºC Shows 50 on the screen When Scenario 7 is selected unit is ready to work as Heat Recovery with 3 Steps Pre heater The connection of the fresh air temperature sensor and the pre heater should be done to the electrical board Below parameters should be set from the servic...

Отзывы: