Applications Digital Output Selection Parameters
4421
420 Exhaust Fan Exit Number
0...12
Relay Selection
4422
421 Supply Fan Exit Number
4423
422 After El.Heater Exit Number
4424
423 Pre El. Heater Exit Number
4425
424 Fresh Air Damper On Exit Number
4426
425 Fresh Air Damper Off Exit Number
4427
426 ByPass Damper On Exit Number
4428
427 ByPass Damper Off Exit Number
4429
428 Exhaust Fan On/Off Exit Number
4430
429 Supply Fan On/Off Exit Number
4431
430 Heating Valve On/Off Exit Number
4432
431 Cooling Valve On/Off Exit Number
4433
432 Cooling/Heating Valve On/Off Exit Number
4434
433 Compressor Exit Number
4435
434 Compressor 4 Way Valve Exit Number
4436
435 Unit On Exit Number
4437
436 Unit in Error Mode Exit Number
4438
437 VRF On/Off Exit Number
4439
438 VRF Heating Exit Number
4440
439
VRF Cooling Soğutma Exit Number
4441
440 Humidifier Exit Number
4442
441 Warning Exit Number
Analog Output Parameters
4451
450 Supply Fan Analog Exit Number
0...10
4452
451 Heating Valve Analog Exit Number
4453
452 Cooling Valve Analog Exit Number
4454
453 Heating/Cooling Valve Analog Exit Number
4455
454 Mixing Damper Analog Exit Number
4456
455 VRF Set Anolog Exit Number
4457
456 VRF On/Off Exit Number