4171
170
Max. Temperature Value for defrost
-400...999
4172
171 Max.Defrost Period
1...100
4173
172 Waiting Time between two defrosts
1…100
Frost Protection Setting Parameters
4174
173
Heating Coil min Temp. Value in case of Frost
-400...999
4175
174
Heating Coil max. Temp. Value in case of Frost
-400...999
4176
175
Exchanger min Temp. Value in case of Frost
-400...999
4177
176
Exchanger max. Temp. Value in case of Frost
-400...999
4178
177 Dirty Filter Warning Time
1...9999
After working for 1200 hours,,this alarm
will appear on screen.
4179
178 Exhaust Fan Air Blowing Control Period
1...9999
4180
179 Supply Fan Air Blowing Control Period
1...9999
Universal Input Check Parameeters
4182
181 Number 1 Universal Inlet
-400...999
4183
182 Number 2 Universal Input
-400...999
4184
183 Number 3 Universal Input
-400...999
4185
184 Number 4 Universal Input
-400...999
4186
185 Number 5 Universal Input
-400...999
4187
186 Number 6 Universal Input
-400...999
4188
187 Number 7 Universal Input
-400...999
4189
188 Number 8 Universal Input
-400...999
4190
189 Number 9 Universal Input
-400...999
4191
190 Number10 Universal Input
-400...999
4192
191 Number 11 Universal Input
-400...999
4193
192 Number 12 Universal Input
-400...999
4194
193 Number 13 Universal Input
-400...999
4195
194 Number 14 Universal Input
-400...999
4196
195 Number 15 Universal Input
-400...999
4197
196 Number 16 Universal Input
-400...999
4198
197 Number 17 Universal Input
-400...999
4199
198 Number 18 Universal Input
-400...999
4200
199 Number 19 Universal Input
-400...999