4022 

21 

Exhaust Fan Thermal Error Info 

0...1 

Exhaust Fan Error Info 

4023 

22 

Supply Fan Thermal Error Info 

0...1 

Supply Fan Error Info 

4024 

23 

Emergency Stop Button Info 

0...1 

Emergency Stop Button Info 

4025 

24 

Low Pressure Info 

0...1 

Low Pressure Info 

4026 

25 

Hıgh Pressure Info 

0...1 

Hıgh Pressure Info 

4027 

26 

Fire Info 

0...1 

Fire Info Entry 

 

4028 

 

27 

 

Frost Thermostate Info 

 

0...1 

Frost Thermostate Info (Valves are open 
and fans are closed during water coil 
application) 

4029 

28 

Compressor Thermal Error Info 

0...1 

Compressor Thermal Info (If there is an 
error on  the compressor, it will be 
stopped.) 

4030 

29 

Phase Error Info 

0...1 

Phase error Info (Unit will be stopped.) 

4031 

30 

Exchanger Frost Info 

0...1 

 

4032 

31 

VRF Error 

0...1 

 

4033 

32 

VRF Defrost 

0...1 

 

 

Unit Analog Entry Registers 

4034 

33 

Humidity Value 

0...1000 

The value should be between  

 321 to 340 . 

4035 

34 

Air Quality Value 

0...1000 

4036 

35 

CO2 Value 

0...1000 

4037 

36 

Return Pressure Value 

0...1000 

 

4038 

37 

Blowing Pressure value 

0...1000 

 

4039 

38 

Anolog 1 Set Value 

 

 

4040 

39 

Analog 2 Set Value 

 

 

4041 

40 

Analog 3 Set Value 

 

 

Mixing Damper  Registers 

4042 

41 

Mixing Damper Mode 

0...1 

 

4043 

42 

Mixing Damper Manual Value 

 

 

Digital Putput Online  Registers 

4044 

43 

Fresh Air/Suction  Damper Motor 

0...1 

0:Off 1:On 

4045 

44 

ByPass Damper Motor 

0...1 

0:Off 1:On 

4046 

45 

Heating/Cooling Coil Valve Exit 

0...1 

0:Off 1:On 

4047 

46 

Heating Coil On/Off  Exit 

0...1 

0:Off 1:On 

4048 

47 

Cooling Coil On/Off  Exit 

0...1 

0:Off 1:On 

4049 

48 

Compressor Exit 

0...1 

0:Off 1:On 

4050 

49 

Compressor 4 way Valve Exit 

0...1 

0:Off 1:On 

4051 

50 

Unit Working Info Exit 

0...1 

0:Off 1:On 

4052 

51 

Unit Error Info Exit 

0...1 

0:Off 1:On 

4053 

52 

Unit Warning Info Exit 

0...1 

0:Off 1:On 

4054 

53 

Exhaust Fan Run Exit 

0...1 

0:Off 1:On 

4055 

54 

Supply Fan Run Exit 

0...1 

0:Off 1:On 

4056 

55 

VRF On Off EXit 

0...1 

0:Off 1:On 

4057 

56 

VRF Heating EXit 

0...1 

0:Off 1:On 

4058 

57 

VRF Soğutma Çıkışı 

0...1 

0:Off 1:On 

4059 

58 

Rotary Exchanger Exit 

0...1 

0:Off 1:On 

4060 

59 

Humidifier Exit 

0...1 

0:Off 1:On 

4061 

60 

Exhaust Fan Instant Exit Value 

0...6 

 

Shows instant values of fan and 
electrical heater 

 

4062 

61 

Supply Fan Instant Exit Value 

0...6 

4063 

62 

Last-Electrical Heater Instant Exit Value 

0...3 

4064 

63 

Pre-Electrical Heater Instant Exit Value 

0...3 

Instant  Accessories Registers 

4065 

64 

Exhaust Fan Analog Exit Value 

0...100 

 
 
 
 

Shows proportional exit values. 

4066 

65 

Supply Fan Analog Exit Value 

0...100 

4067 

66 

Proportional  Heating Valve Exit Value 

0...100 

4068 

67 

Proportional  Cooling Valve Exit Value 

0...100 

4069 

68 

Proportional  Heating/Cooling Valve Exit Value 

0...100 

Содержание CONTROL KIT 5

Страница 1: ...JAKKA CONTROL KIT 5 USER MANUAL ...

Страница 2: ...ust and supply fans Working of the unit in Automatic Manual Modes Heating Cooling Fan Modes Room Temperature Sensor User Friendly Design Minimum ve Maximum Set Temperature Limit Constant HVAC R Images Weekly Programming 1 ROOM THERMOSTATE ...

Страница 3: ... air damper bypass damper heating coil cooling coil and also EC fans Main Features Filter Alarm According to Pre set Time counter Pre set Service Time Pre programmed scenario selection via room thermostate Adjustable Mode selection Auto Heating Auto Cooling Manual Heating Manual Cooling Fan Mode Restart with the last paremeters in case of power shortage Connection to building management system Mod...

Страница 4: ...10A 6 Steps Consumption Max 5VA Connection 1 5mm clips Functional Specs On Off via BMs Embedden temperature sensor to room thermostate Control Of Duct Type Temperature Sensor Fresh Air Damper Bypass Air Damper External Sensor Connection NTC 10K 6 Steps Manuael or Auto Speed Selection for Exhaust and Supply Fans seperately Unit On Off info Weekly Programming Carbondioxide Air Quality Sensor Control...

Страница 5: ...01 by using UP and DOWN buttons then press Mode OK button Set hour minute by pressing UP and DOWN buttons then go on by pressing Mode OK Set day month by pressing UP and DOWN buttons then go on by pressing Mode OK Set year by pressing UP and DOWN buttons then go on by pressing Mode OK Set name of the day by pressing UP and DOWN buttons then go on by pressing Mode OK C CHANGING UNIT MODE The mode c...

Страница 6: ...on the screen will be deleted after 2 seconds Then press any button All buttons will be functional again G HOW TO RESET ALARM CODE If Err 0001 alarm or any other alarm code blinking on screen Press FAN and UP buttons simultaneously H HOW TO RESET FILTER DIRTINESS COUNTER When you got 0001 warning on the screen You can reset it by pressing FAN and Mode OK buttons simultaneously Note You can change ...

Страница 7: ...o Parameter you want to change by using UP and DOWN buttons then press Mode OK button Change the parameter by using UP and DOWN buttons then press Mode OK button Get out of menu by pressing ON OFF button Caution All the changes on the service menu should be done by authorized personnel The damage and problems causing by unauthorized changes on the service menu will be on user s responsibility ...

Страница 8: ...nd DOWN and press Mode OK Note Service menu password is 58 Then go to Parameter 118 by using UP and DOWN buttons then press Mode OK button Change the parameter by using UP and DOWN buttons then press Mode OK button Parameter 118 could be one of below numbers 0 Room thermostate 1 Return Air 2 Supply Air 3 Outside Air Get out of menu by pressing ON OFF button Note Selected sensor should be connected...

Страница 9: ... OK Change the value according to table below by using UP and DOWN and press Mode OK Check out from the menu by using ON OFF button Fan Step Parameters 130 Exhaust Fan 0 Step Value 0 100 131 Exhaust Fan 1 Step Value 132 Exhaust Fan 2 Step Value 133 Exhaust Fan 3 Step Value 134 Exhaust Fan 4 Step Value 135 Exhaust Fan 5 Step Value 136 Exhaust Fan 6 Step Value 137 Supply Fan 0 Step Value 0 100 138 S...

Страница 10: ...Caution If the fans run before damper opens fan motors could be broken M ADDING PRE HEATER You can add preheater by configuring the below parameters When the unit is connected to power supply press UP and DOWN buttons simultaneously Enter service menu password 58 by using UP and DOWN and press Mode OK Go and change to below parameter by using UP and DOWN and press Mode OK Change the value by using...

Страница 11: ...ng FAN and UP buttons simultaneously If there is a broken component replace it with a new one If there is an obstacle at the duct systemi clean it a for a better air flow E 0016 Supply Air Flow Error Check the exhaust fan connection cables filter and ducting If 11lla re fine reset the alarm by pressing FAN and UP buttons simultaneously If there is a broken component replace it with a new one If th...

Страница 12: ... 4004 3 Exhaust Fan Manual Speed Value 0 6 4005 4 Supply Fan Manual Speed Value 0 6 Temperature Parameters 4006 5 Unit Ambient Temperature 400 999 280 value means 28 ºC 4007 6 Panel Ambient Temperature 400 999 Temperatıre on the propanel 4008 7 Exhaust air temperature 400 999 Exhaust air temperature 4009 8 Supply air temperarure 400 999 If there is no temperature value on the unit the value will b...

Страница 13: ...tal Putput Online Registers 4044 43 Fresh Air Suction Damper Motor 0 1 0 Off 1 On 4045 44 ByPass Damper Motor 0 1 0 Off 1 On 4046 45 Heating Cooling Coil Valve Exit 0 1 0 Off 1 On 4047 46 Heating Coil On Off Exit 0 1 0 Off 1 On 4048 47 Cooling Coil On Off Exit 0 1 0 Off 1 On 4049 48 Compressor Exit 0 1 0 Off 1 On 4050 49 Compressor 4 way Valve Exit 0 1 0 Off 1 On 4051 50 Unit Working Info Exit 0 1...

Страница 14: ...88 87 Month Setting 1 12 4089 88 Year Setting 0 99 4090 89 Hour setting 0 23 4091 90 Minute Setting 0 59 4092 91 Seconds setting 0 59 4093 92 Setting day of the week 1 7 1 Sunday 2 Monday 3 Tuesday 4 Wednesday 5 Thursday 6 Friday 7 Saturday 4094 93 Instant Weekly Programming Check 0 2 0 No weekly Programming 4095 94 RTC Module 0 1 1 Unit Works and it has a weekly programming 4096 95 Error Value 0 ...

Страница 15: ...ents after waiting for the period defined here Auto Mode Fan Setting Parameters 4121 120 Auto Mod Fan Min Speed 0 6 The minimum speed for fans at auto mod 4122 121 Full Auto Mod Fan Working Stage 0 1 0 Normal 1 Working Continously 4123 122 Full Auto Mod Exhaust Fan Value 0 100 Working value for Exhaust Fan 4124 123 Full Auto Mod Supply Fan Value 0 100 Working value for Supply Fan 4125 124 Full Per...

Страница 16: ...eriod 4150 149 Heater Limiting according to Fan 0 1 Pre Heater Setting Parameters 4151 150 Pre Heater Delay time at Start 1 999 Sec 4152 151 Pre Heater Delay time at Stop 1 999 Sec 4153 152 Pre Heater Hysteresis Value 1 100 100 value means 10 0ºC 4154 153 Pre Heater Steps as Temperature 4155 154 Pre Heater Step Quantity 0 3 Last Heater Setting Parameters 4156 155 After Heater Opening Delay Time 1 ...

Страница 17: ...Universal Input Check Parameeters 4182 181 Number 1 Universal Inlet 400 999 4183 182 Number 2 Universal Input 400 999 4184 183 Number 3 Universal Input 400 999 4185 184 Number 4 Universal Input 400 999 4186 185 Number 5 Universal Input 400 999 4187 186 Number 6 Universal Input 400 999 4188 187 Number 7 Universal Input 400 999 4189 188 Number 8 Universal Input 400 999 4190 189 Number 9 Universal In...

Страница 18: ...9999 9999 4229 228 Number 8 Analog Input 9999 9999 Analog Output Check Parameters 4232 231 Number 1 Analog Output 9999 9999 4233 232 Number 2 Analog Output 9999 9999 4234 233 Number 3 Analog Output 9999 9999 4235 234 Number 4 Analog Output 9999 9999 4236 235 Number 5 Analog Output 9999 9999 4237 236 Number 6 Analog Output 9999 9999 4238 237 Number 7 Analog Output 9999 9999 4239 238 Number 8 Analog...

Страница 19: ... 279 Uın19 Input On Off Selection Universal Digital Input Signal Detecting Delay Setting Parameters 4282 281 Uın1 Input Signal Detecting Delay 0 999 4283 282 Uın2 Input Signal Detecting Delay 4284 283 Uın3 Input Signal Detecting Delay 4285 284 Uın4 Input Signal Detecting Delay 4286 285 Uın5 Input Signal Detecting Delay 4287 286 Uın6 Input Signal Detecting Delay 4288 287 Uın7 Input Signal Detecting...

Страница 20: ...lue 9999 9999 4333 332 Analog Input 2 Maximum Value 9999 9999 4334 333 Analog Input 3 Maximum Value 9999 9999 4335 334 Analog Input 4 Maximum Value 9999 9999 4336 335 Analog Input 5 Maximum Value 9999 9999 4337 336 Analog Input 6 Maximum Value 9999 9999 4338 337 Analog Input 7 Maximum Value 9999 9999 4339 338 Analog Input 8 Maximum Value 9999 9999 4340 339 Analog Input 9 Maximum Value 9999 9999 An...

Страница 21: ...nal Detecting Delay 2 Supply Air Temperature 4405 404 UI 4 Input Signal Detecting Delay 3 Fresh Air Temperature 4406 405 UI 5 Input Signal Detecting Delay 4 Water Coil Temperature 4407 406 UI 6 Input Signal Detecting Delay 5 Evaporator Temperature 4408 407 UI 7 Input Signal Detecting Delay 6 Condensor Temperature 4409 408 UI 8 Input Signal Detecting Delay 7 Exchanger Temperature 4410 409 UI 9 Inpu...

Страница 22: ...ing Valve On Off Exit Number 4433 432 Cooling Heating Valve On Off Exit Number 4434 433 Compressor Exit Number 4435 434 Compressor 4 Way Valve Exit Number 4436 435 Unit On Exit Number 4437 436 Unit in Error Mode Exit Number 4438 437 VRF On Off Exit Number 4439 438 VRF Heating Exit Number 4440 439 VRF Cooling Soğutma Exit Number 4441 440 Humidifier Exit Number 4442 441 Warning Exit Number Analog Ou...

Страница 23: ...ery with Dx Coil VRF 13 Heat Recovery with On Off Valved Water coil 4Pipe 14 Heat Recovery with EC Fan and 3 Steps Electrical Heater 15 Heat Recovery with EC Fan and On Off Valved Water Coil 2Pipe 16 Heat Recovery with EC Fan and On Off Valved Water Coil 4Pipe To change the scenario When the unit is connected to power supply press UP and DOWN buttons simultaneously Enter service menu password 58 b...

Страница 24: ...he electrical board comes with Scenario Number 4 as default To change the scenario please follow the steps defined in Changing the Scenario When Scenario 2 is selected unit is ready to work as Heat Recovery with 3 Steps Electrical Heater With Fresh Air Damper In this mode exhaust and supply fans and after heater can be controlled Temperature is measured by room thermostate If room temperature is m...

Страница 25: ...Heater With By Pass Damper Heat Recovery with 1 Step Pre Heater 2 Steps After Heater mode Works according to set temepareture and control exhaust ans supply fans and after heater Pre heater works according to fresh air sensor Inside air temperature is measured by room thermostate If room temperature is measured below set value temperature will be increased by using after heater If room temperature...

Страница 26: ... screen 153 Pre Heater Step Difference as Temperature 5 ºC Shows 50 on the screen 160 Pre Heater Set Temperature 5 ºC Shows 50 on the screen The connection of the fresh air temperature sensor and the electrical heater should be done to the electrical board Below parameters should be set as follows from the service parameters menu Please follow the instructions described at I Entering to Service Me...

Страница 27: ... please follow the steps defined in S Changing the Scenarios Default Values for Pre Heater Parameter Description Default Value Detail 152 Pre Heater Hysterises Value 2 ºC Shows 20 on the screen 153 Pre Heater Step Difference as Temperature 5 ºC Shows 50 on the screen 160 Pre Heater Set Temperature 5 ºC Shows 50 on the screen When Scenario 6 is selected unit is ready to work as Heat Recovery with 2...

Страница 28: ...ows 20 on the screen 153 Pre Heater Step Difference as Temperature 5 ºC Shows 50 on the screen 160 Pre Heater Set Temperature 5 ºC Shows 50 on the screen When Scenario 7 is selected unit is ready to work as Heat Recovery with 3 Steps Pre heater The connection of the fresh air temperature sensor and the pre heater should be done to the electrical board Below parameters should be set from the servic...

Отзывы: