4022
21
Exhaust Fan Thermal Error Info
0...1
Exhaust Fan Error Info
4023
22
Supply Fan Thermal Error Info
0...1
Supply Fan Error Info
4024
23
Emergency Stop Button Info
0...1
Emergency Stop Button Info
4025
24
Low Pressure Info
0...1
Low Pressure Info
4026
25
Hıgh Pressure Info
0...1
Hıgh Pressure Info
4027
26
Fire Info
0...1
Fire Info Entry
4028
27
Frost Thermostate Info
0...1
Frost Thermostate Info (Valves are open
and fans are closed during water coil
application)
4029
28
Compressor Thermal Error Info
0...1
Compressor Thermal Info (If there is an
error on the compressor, it will be
stopped.)
4030
29
Phase Error Info
0...1
Phase error Info (Unit will be stopped.)
4031
30
Exchanger Frost Info
0...1
4032
31
VRF Error
0...1
4033
32
VRF Defrost
0...1
Unit Analog Entry Registers
4034
33
Humidity Value
0...1000
The value should be between
321 to 340 .
4035
34
Air Quality Value
0...1000
4036
35
CO2 Value
0...1000
4037
36
Return Pressure Value
0...1000
4038
37
Blowing Pressure value
0...1000
4039
38
Anolog 1 Set Value
4040
39
Analog 2 Set Value
4041
40
Analog 3 Set Value
Mixing Damper Registers
4042
41
Mixing Damper Mode
0...1
4043
42
Mixing Damper Manual Value
Digital Putput Online Registers
4044
43
Fresh Air/Suction Damper Motor
0...1
0:Off 1:On
4045
44
ByPass Damper Motor
0...1
0:Off 1:On
4046
45
Heating/Cooling Coil Valve Exit
0...1
0:Off 1:On
4047
46
Heating Coil On/Off Exit
0...1
0:Off 1:On
4048
47
Cooling Coil On/Off Exit
0...1
0:Off 1:On
4049
48
Compressor Exit
0...1
0:Off 1:On
4050
49
Compressor 4 way Valve Exit
0...1
0:Off 1:On
4051
50
Unit Working Info Exit
0...1
0:Off 1:On
4052
51
Unit Error Info Exit
0...1
0:Off 1:On
4053
52
Unit Warning Info Exit
0...1
0:Off 1:On
4054
53
Exhaust Fan Run Exit
0...1
0:Off 1:On
4055
54
Supply Fan Run Exit
0...1
0:Off 1:On
4056
55
VRF On Off EXit
0...1
0:Off 1:On
4057
56
VRF Heating EXit
0...1
0:Off 1:On
4058
57
VRF Soğutma Çıkışı
0...1
0:Off 1:On
4059
58
Rotary Exchanger Exit
0...1
0:Off 1:On
4060
59
Humidifier Exit
0...1
0:Off 1:On
4061
60
Exhaust Fan Instant Exit Value
0...6
Shows instant values of fan and
electrical heater
4062
61
Supply Fan Instant Exit Value
0...6
4063
62
Last-Electrical Heater Instant Exit Value
0...3
4064
63
Pre-Electrical Heater Instant Exit Value
0...3
Instant Accessories Registers
4065
64
Exhaust Fan Analog Exit Value
0...100
Shows proportional exit values.
4066
65
Supply Fan Analog Exit Value
0...100
4067
66
Proportional Heating Valve Exit Value
0...100
4068
67
Proportional Cooling Valve Exit Value
0...100
4069
68
Proportional Heating/Cooling Valve Exit Value
0...100