Operation Manual ITW GSE 6400 Tier 4
2) Preparation for Storage
A generator set in storage or removed from operation, has special precautions that should be taken to
protect internal and external parts from rust, corrosion, and gumming in the engine fuel system.
a) General
Open battery disconnect switch and disconnect battery negative terminal at battery.
1) The unit should be prepared for storage as soon as possible after being removed from
service.
2) The unit should be stored in a building that is dry and can be heated during winter months.
3) Moisture-absorbing chemicals should be used where excessive dampness is a problem;
however, the unit must be completely packaged and sealed if moisture-absorbing chemicals
are to be effective.
b) Temporary Storage (30 days or less)
1) Lubricate unit completely in accordance with instructions in Chapter 2-2 Page 2. This will
include changing engine oil, and all filter elements.
2) Start engine and operate a minimum of two minutes so all internal engine components are
coated with new oil. (Note: if unit is operated outside of diagnostic mode, it will run for 30
seconds in cool down mode after stop button is pressed.)
NOTE: Do not
drain fuel system or crankcase after this run.
3) Cooling system antifreeze solution
must
be adequate to protect below lowest temperatures
expected during storage period. Be sure solution is thoroughly mixed.
4) Clean exterior of engine. Dry with clean rags and compressed air.
5) Seal all engine openings. Use water-proof, vapor-proof material strong enough to resist
puncture damage from air pressure changes.
OM2248 Rev B
Page 28 of 104
Содержание 6400 Tier 4
Страница 49: ...Operation Manual ITW GSE 6400 Tier 4 c Black Box OM2248 Rev B Page 48 of 104 ...
Страница 53: ...Operation Manual ITW GSE 6400 Tier 4 OM2248 Rev B Page 52 of 104 ...
Страница 96: ...Operation Manual ITW GSE 6400 Tier 4 This page is intentionally left blank OM2248 Rev B Page 95 of 104 ...
Страница 104: ...OM2248 Rev B Page 103 of 104 ...