Doc. CEI12166
Rev. 1
Pag. 30 Of 47
- Results: Save.
The default timing is shown below.
If these values match with what you want to do, you can immediately start the test; else, you can load a
previously saved setting, or you can enter the menu, modify the desired parameters and then save the
setting, before proceeding.
2.3.5.11 Tests header
This selection allows setting the header of a single test or of all tests performed on the CB: time
measurement, contact resistances.. Pressing it, the following window is displayed.
Data can be keyed on as follows:
. Using the keypad: rules are the same as portable phones;
. Using the knob to select the digit on last line.
Pressing OK after edit, all next tests will be assigned the same header, until it is modified.
C DURATION: 0,5 s
OC DELAY: 0,3 s
CO DELAY: 0,6 s
RECORDING DURATION: 1 s
O DURATION: 0,1 s
OPEN
CLOSE
PRE-TRIGGER: 0,1 s