2.3.6 Magnifying lenses 

 
Pressing these lenses, the area between the cursors is enlarged or reduced. This allows magnifying the 
part of interest of the diagram. 

2.3.7 t1, t2, dt 

 
If  t1  and  t2  are  selected,  after  the  test  the  values  of  t1  and  t2,  corresponding  to  cursors  1  and  2,  are 
displayed, along with the delay between them. To move the cursors, select t1 or t2 and press the knob: 
while t1 or t2 is shown reversed, moving the knob you can move the corresponding cursor, close to the 
position of interest. 

2.3.8 Printer 

 
Selecting the printer, the test set verifies if the optional thermal printer is available: if it is, the printout 
is performed on it, else the print message is sent to the selected interface. The following window allows 
selecting:  All  data;  Header;  Trigger  options;  Breaker  options;  Analog  settings;  Recorder  options;  
Channel Set; Diagram; Time results table; Movement result table. 

2.3.8 Left column 

 
The left column is modified according to the View selections.  The “Armed” selection means that the 
test  set  is  ready,  and  that  it  will  start  measuring  as  soon  as  the  trigger  will  be  sensed  on  the  SLAVE 
input socket. 
 

2.4

 

CB

 CONNECTIONS

 

2.4.1 Main CB contacts. 

 
The  first  operation  is  to  connect  CBA1000  to  main  CB  contacts.  To  this  purpose,  are  provided  six 
sockets in all, marked  A1, B1, C1, and A2, B2, C2. The first ones are used for one-chamber CB; the 
others are used for two-chamber CB. 
 
For the test of the pre-insertion resistor there is no further connection. 
 
LED’s by the side are two: RED (above) if the contact is OPEN, and GREEN (below) if it is closed. 
The pre-insertion resistor is sensed as Open. 
 

 

 

Содержание CBA1000

Страница 1: ...zioni Sistemi Automatici S r l VIA BERGAMO 41 21020 TAINO VA ITALY OFFICES TEL 39 0331 956081 FAX 39 0331 957091 LAB TEL 39 0331 956483 E MAIL isa isatest com WEB www isatest com DATE 12 12 2005 DOC M...

Страница 2: ...2 dt 31 2 3 8 Printer 31 2 3 8 Left column 31 2 4 CB CONNECTIONS 31 2 4 1 Main CB contacts 31 2 4 2 Coil drivers 32 2 4 3 Auxiliary CB contacts 33 2 4 4 Travel transducer or analog input 33 2 4 5 Micr...

Страница 3: ...Doc CEI12166 Rev 1 Pag 3 Of 47 3 6 2 Calibration procedure 44 APPENDIX 1 SPARE PARTS LIST 46 APPENDIX 2 TEST SET SCHEMATIC 47...

Страница 4: ...of help or I ignore it This is why I decided to split the CBA1000 manual in three specification with all performance details introductory guide with the device description application manual with inst...

Страница 5: ...insertion resistor Four digital event input circuits For the main and event inputs measurement of delays with respect to coil currents or other references The Open or Closed state of main and event i...

Страница 6: ...ned to ensure safe operation in the noisy environment of HV and MV substations The instrument is housed in a transportable aluminium box that is provided with removable cover and handles for ease of t...

Страница 7: ...d T5A incorporated in the supply socket 2 Earth socket 3 Power on switch with light 4 Buzzer it tells that the test is about to be started 5 MENU control knob with switch 6 Display before testing it a...

Страница 8: ...ses 2 and 3 one side will be connected to the positive or to the negative of the DC supply 25 Type of test selection pushbutton as pressed lights 26 move in a circular way If unused the selection perf...

Страница 9: ...nt selection and START 27 with the light 28 that starts the test Test selections are performed by the keypad 7 control knob 5 and display 6 As With portable phones pressing a button you access in sequ...

Страница 10: ...ing can be performed else selecting the arrow the menu returns to the main window 2 3 1 Set This selection is a short cut to the Setup options selection of the Menu see below 2 3 2 Res This selection...

Страница 11: ...On the same result you can temporarily select to view on trace only so that it can be examined at ease 2 3 5 Menu With this selection the following window is opened 2 3 5 1 Test diagram This is the s...

Страница 12: ...contact Auxiliary lines are Thin Open Thick Closed Next lines are the coil currents profiles they are four if the option is installed The time base is the test duration with a scale that corresponds t...

Страница 13: ...der test results Also changing the current threshold changes the timing result as the current increases slowly because of the coil inductance With CBA1000 coil driving is electronic the voltage edge i...

Страница 14: ...er Slave units will measure the timing on Main auxiliary and analog inputs but don t generate coil driving signals This feature allows to test circuit breakers with more than two chambers per phase or...

Страница 15: ...ator acts on SEL opening this window the performed selection is repeated This selection is useful in case of Definition of Open commands if the of four coil drive option is available Definition of the...

Страница 16: ...ated With the Sequence selection the user can edit the desired test sequence This gives the following possibilities Issue a sequence of Open and Close commands up to 200 commands can be programmed Wit...

Страница 17: ...The timing definition can be displayed pressing HELP diagram the following window is displayed As you see from timing definitions it is possible to superimpose a Close command to the Open command this...

Страница 18: ...le to program a first recording duration then a dead time then the second recording duration In this mode coil currents and the analog input are not monitored If the box is checked the selection windo...

Страница 19: ...insertion resistor test In the second and third set of selections it is possible to enable the test of auxiliary inputs to label them and to select whether the contact is wet or dry A1 A2 can be diff...

Страница 20: ...is displayed It is possible to label the input and to select the voltage range that must be greater than the nominal coil current else the recording will be cut saturated at the selected range value a...

Страница 21: ...Use auxiliary 5 V generator for travel transducer this means that you have connected the transducer to the 5 V output sockets else you have to input the external supply voltage value The Pressure tra...

Страница 22: ...erformed connecting CBA1000 to the test sample and measuring its resistance Test samples can be joints main contacts and so on Main contacts resistance is measured in the closed position With the Dyna...

Страница 23: ...ng resistance range is displayed The Test mode selection allows to perform a single measurement or to measure in sequence the resistance of all CB contacts If the selection is Test on breaker phase it...

Страница 24: ...sequence the resistance of all CB contacts If the selection is Test on breaker phase it is possible to specify the CB phase and contact under test test results will be displayed in the summary table T...

Страница 25: ...ke some time in the meanwhile the following message is displayed If the memory is full the following message warns the operator Usually test results are deleted after downloading them into the PC Also...

Страница 26: ...Pag 26 Of 47 2 3 5 9 Preferences This selection allows defining some ancillary selections pressing it the following window is displayed Date and time can be set with the first selection the following...

Страница 27: ...contrast can be adjusted pressing on the and keys The backlight duration selection is provided for the case of battery operation as the backlight sinks an important amount of power With the Language s...

Страница 28: ...emory Any setting can be saved to and recalled from the memory Up to 64 settings can be stored and recalled Settings are permanently stored in the memory new settings can be written to the same addres...

Страница 29: ...ion it is possible to recall the default setting that cannot be modified This setting is loaded at power on Trigger options internal trigger Test option Open Close Open Recording options O C delay 0 3...

Страница 30: ...der This selection allows setting the header of a single test or of all tests performed on the CB time measurement contact resistances Pressing it the following window is displayed Data can be keyed o...

Страница 31: ...the selected interface The following window allows selecting All data Header Trigger options Breaker options Analog settings Recorder options Channel Set Diagram Time results table Movement result tab...

Страница 32: ...oils There are four groups marked C Close coil O1 Open coil or phase A Open coil with four coil option O2 and O3 if the option is available else not connected One side of the coil driver shall be conn...

Страница 33: ...vement There are two sockets with a protected 5 V output that serves to polarize the transducer the cursor is connected to the input Else it is possible to connect the input to any voltage that is des...

Страница 34: ...turn ON if some does not it is faulty If something is wrong the operator is alerted by a message At the end of it default selections are active CBA1000 displays the first window explained in the MENU...

Страница 35: ...re shooting at us see if the following instructions can serve you to fix the problem If not e mail us the problem not forgetting to mention the unit s serial number our business is to minimize your do...

Страница 36: ...The microprocessor board 61 and the optional micro Ohmmeter auxiliary board 65 are connected to the front panel board 60 and screwed to it Other cards are kept in place by means of L shaped supports...

Страница 37: ...nnections At power on does not turn on Mains supply fuse open Check the fuse for other problems see 3 4 1 The diagnostic is not completed the test set is locked Fault on the DC to DC converter See 3 4...

Страница 38: ...s on both edges Fit the replacement one and verify if the test set is OK you can continue else the test set needs to be returned 3 4 3 The control knob does not operate First of all check that the kno...

Страница 39: ...ing is correct and the LED does not turn on then there is a faulty LED for the repair the test set needs to be returned If there is a doubt about the timing metered by CBA1000 please press the Set pus...

Страница 40: ...CAPACITOR IS COMPLETELY DESCHARGED given the big capacitance value it takes a long time to dissipate its energy The operating voltage is 10 V if it is not completely discharged use a 100 Ohm 10 W resi...

Страница 41: ...et to compile it With the instrument should come the mains supply cable and the interface cables The user s manual originally delivered with the test set is not necessary Cover the instrument with a p...

Страница 42: ..._____________________________ HOW DID IT OCCUR ______________________________________________________ __________________________________________________________________________ _______________________...

Страница 43: ...n also input your password that is blank at the beginning After this the first message after power on is Input the password Take care because if you lose it it is hard to recover the operation 3 6 CAL...

Страница 44: ...ut a jumper on the coil driver then select the offset channel the following window is displayed If you check Fine the offset is automatically adjusted press Set to save the new correction For the ampl...

Страница 45: ...generated by a relay test set Press Measure and then apply voltages as displayed then set the measurement If the micro Ohmmeter is to be calibrated the following window is displayed The offset calibr...

Страница 46: ...ts 1 N 10 Fuses in the supply socket 1 rated T5A code XFU 2 N 10 Fuses of the 5 V DC voltage 20 rated F100mA code XFU 3 N 1 Encoder with switch for MENU control knob 5 code XCM10160 4 N 1 Printed circ...

Страница 47: ...Doc MIE10166 Rev 1 Page 47 of 47 APPENDIX 2 TEST SET SCHEMATIC...

Отзывы: