background image

 

 
SEPAMAT F-SC_Manual_Vers.1.0e_en 

 

13 

 

5.1.3 Self-initialization 

 

Each 

SMT-F-SC

 pump is factory set for the initial pump control! 

 
The  below  described  self-initialization  must  be  performed 

only

  when  a  program  RESET  was 

conducted or if a new pump or a new pump control was installed. 
In  this  automatic  initialization,  the  characteristic  current  values  are  analysed  at  different  operating 
parameters, which form the basis of the speed controller. 
 

1.) Make  sure  the  pump  is  automatically  primed  with  water  (see  section  7.1)  when  it  first  begins 

operation.  

 
2.) Open the air vent and let water flow out until there is no more air in the system. Then close the 

pressure shutoff valve (pressure increases). 

 
3.) In case the pressure of the system is > 3 bar, the stopcock must be opened again to reduce the 

pressure to < 3 bar. 

 

4.) Press 

START

  to  start  the  self-initialization.  After  about  two  minutes  (total  pressure  range  of  the 

pump is analysed) the initialization is finished. The segmented LED indicator lights up one time, 
from 0 all the way to 10 bar and the pump stops (LED Minimum Flow lights up). 

 
5.) The  self-initialization  is  now  finished  and  the  start-up  procedure  can  follow  (see  section  7.2). 

Changing the predefined discharge pressure of 3 bar is possible, if necessary, in 0.5 bar steps 

by  pressing  the 

+

  or 

    button  (the  pressure  setting  has  been  saved  once  the 

segmented LED no longer blinks). 

 

Command 

Button combination 

RESET 
(to restore factory 
settings) 

 

    &     

STOP

   press simultaneously for 5 seconds (total 

segmented LED indicator blinks once). 

Pull the mains plug and wait until all the LEDs are off. 

SELF-INITIALIZATION 

Plugin the mains plug. 

Press   

START

  to start the self-initialization. 

 

Checking the pump start and stop 

At the end of the self-initialization, test the start and stop of the pump system by turning on one or 
more  fixtures. When  the  pump  stops,  the  yellow  LED  Minimum  Flow  will  flash. When  the  fixtures 
are opened, the pump must independently start again. 
 

Checking the dry-running protection 

In cases of water shortage, the pump must stop after 40 secs and the red LED Dry Working turn 
on. This check is best performed by shutting the mains water supply valve and opening a fixture. 
 
 

Содержание SEPAMAT F-SC 20

Страница 1: ...WATER WE RE IN OUR ELEMENT www intewa de SEPAMAT F SC Installation and user manual WATER WE RE IN OUR ELEMENT www intewa com...

Страница 2: ...c controller 17 5 3 Components of the multistage pump 18 5 4 Components of separation chamber 19 6 Installation instructions 20 6 1 Wall mounting 20 6 2 Connection to the mains water line 21 6 3 Insta...

Страница 3: ...rom the separation chamber to the consumers The water level in the separation chamber is controlled by a floating valve The drinking water supply and emergency overflow are connected to the separation...

Страница 4: ...mp never dry runs All operating parameters such as time delay idle and load power consumption and response time for the dry running are specified by the controller Bluetooth connection Two or three un...

Страница 5: ...ns at the mains water pipeline system can only be performed by a qualified installation company A floor drain has to be provided near the installation site which can collect inadvertent water discharg...

Страница 6: ...SC_Manual_Vers 1 0e_en 5 3 Scope of delivery Separation unit SEPAMAT F SC Wall mounting material installation and user manual Standard accessory A Mains water connection Standard accessory B Pressure...

Страница 7: ...ower max 0 8 kW max 1 25 kW Supply voltage frequency 3 x 230 V 0 55Hz 3 x 230 V 0 55Hz Rated current max 2 6 A max 3 5 A Discharge pressure 2 0 4 5 bar adjustable 2 0 5 5 bar adjustable Max flow rate...

Страница 8: ...SEPAMAT F SC_Manual_Vers 1 0e_en 7 4 1 Device overview and dimensions Left side view Right side view Front view...

Страница 9: ...er 3 Vent cock 4 Pressure line shut off valve 1 female 5 Pump controller 6 Pressure sensor 4 20 mA male 7 Separation chamber 8 Stopcock for mains water 3 4 female 9 Mains water floating valve 10 3 2 w...

Страница 10: ...he requirements of the following EU directives EG Directives for machines 89 392 EWG in accordance with 91 368 EWG EG Low voltage directives 73 23 EWG EG Directives for electromagnetic compatibility 8...

Страница 11: ...lization or after a RESET STOP STOP instantaneous stop of the pump 5 Overview of components The SMT F SC has a modular design Each component can be separately exchanged 5 1 Components of the pump cont...

Страница 12: ...steady Pump stopped due to flow rate below defined minimum see setting F1 Yellow flashing Minimum flow rate reached defined time delay is active see setting F14 Dry Working Dry Working Red flashing P...

Страница 13: ...e disconnected and you have to wait for at least 2 minutes until all LEDs turn off internal capacitors are discharged You may open the case only after this To do this you have to demount the complete...

Страница 14: ...hts up one time from 0 all the way to 10 bar and the pump stops LED Minimum Flow lights up 5 The self initialization is now finished and the start up procedure can follow see section 7 2 Changing the...

Страница 15: ...n of setting mode STOP press simultaneously for about 3 seconds until the total segmented LED indicator blinks once and the setting F1 is displayed Display next setting value Keep the STOP button pres...

Страница 16: ...on direction 0 1 0 1 0 F6 Starting RPM ramp up RPM during acceleration 1000 10000 RPM s Each step 500 3000 RPM s F7 Maximum operating pressure Maximum system pressure that should not be exceeded 2 10...

Страница 17: ...h step 1 sec 12 sec F16 Dry running time delay Setting for time delay on the dry running condition before stopping pump 10 100 sec Each step 5 sec 40 sec F17 Master Slave group communication Operating...

Страница 18: ...e Connection description Pos Board code Connection description 1 2 3 4 5 6 7 8 9 10 11 NE PE ST PE NE bl NE ST bl NE ST br ST1 br PUIN1 ST2 grey PUIN2 ST3 black PUIN3 Ground mains connection Ground pu...

Страница 19: ...DED 1 pcs 1 380 CAPACITOR 47 CAPACITOR ZBR 1 ZBR 1 16 16 O RING NOZZLE 1 pc 1 84 84 PLUG FRONT 1 pc 1 88 88 SHUTTER 1 pc 1 490 490 RUBBER SPACER 1 pc 1 89 89 SPRING SHUTTER 1 pc 1 370 370 SELF PRIMING...

Страница 20: ...g valves closed backside of the container The correct distance of the float 5 to the horizontal lever is factory set at 8 5 cm Note If an overflow occurs due to continuous dripping from the valve the...

Страница 21: ...C is mounted on a wall with the supplied wall bracket The lid and lateral distances indicated should be adhered to when mounting to provide clear maintenance access The SMT F SC is wall mounted in suc...

Страница 22: ...ly is done with the provided flexible hose and stopcock Screw the gland screw into the chamber connection and carefully tighten with a fixed wench Note The flexible hose must not be overtightened as t...

Страница 23: ...nnected to the pump controller The flexible hose and the shut off valve then connect to the pressure line set and the pressure line Attention For optimal and efficient pressure control an expansion ve...

Страница 24: ...ecting to a drainage system in order to prevent backflow of drainage water from the open sewer line design according to the DIN EN 1717 entering the SMT F SC The position of the backwater level determ...

Страница 25: ...n this case the pump doesn t need to be filled up with water by hand Attention The pump must not be dry running 2 Close the pressure line shut off valve 3 Open the air vent hold a bucket of water unde...

Страница 26: ...e all the fixtures The pump will now automatically switch off when the maximum system pressure is reached The green LED on the pump controller indicates that the pump is ready to use In case of a prob...

Страница 27: ...defined by I2t algorithm to protect the motor insulation for correct functioning the rated current must be set F2 A6 Pressure switch malfunction In case of a problem or failure of the pressure switch...

Страница 28: ...will follow After 5 trials the alarm indicator will become permanent and a manual restart will be necessary press STOP then START 9 Trouble shooting Description Cause Solution Pump does not start Dry...

Страница 29: ...r is in the separation chamber Check mains water pressure clean the filter sieve in the mains water valve see section 5 4 10 Maintenance The SMT F SC operates without regular maintenance At minimum ch...

Страница 30: ...r customers in Germany For any queries ordering of spare parts as well as in case of service kindly contact INTEWA GmbH directly quoting your product s model and identification numbers and the purchas...

Страница 31: ...ever fail the others simply take on the load Through Bluetooth the automatic cycling start up of the pumps the peak load connection and the operating pressure settings are aligned and transferred wir...

Страница 32: ...to use The pumps will automatically start as soon as a decrease in pressure is detected 4 The desired operating pressure can be adjusted by pressing or on any one pump controller The Bluetooth connec...

Отзывы: