SEPAMAT F-SC_Manual_Vers.1.0e_en
11
LED-Indicator
Description
POWER
POWER
Green, steady:
Inverter voltage supply is ON
PUMP ON
PUMP ON
Green, steady:
Pump ON
Green, flashing:
Enable OFF condition
ALARM
ALARM
Red, steady:
Pump stopped due to a malfunction
Restart necessary (STOP then START)
Red, flashing:
Pump stopped due to a malfunction (auto restart)
Minimum
Flow
Minimum Flow
Yellow, steady:
Pump stopped due to flow rate below defined
minimum
(see setting F1)
Yellow, flashing:
Minimum flow rate reached, defined time-delay is
active (see setting F14)
Dry
Working
Dry Working
Red, flashing:
Pump stopped due to dry running, currently in one of
four automatic 15 min restart periods
Red, steady:
Final stop after 5
th
automatic restart malfunction
Segmented LED indicator
- indicator of discharge pressure in 0.5 bar steps
- indicates the adjustment of pressure for 3 seconds after pressing
+
or
- settings indicator in setting mode
- indicator of alarms based on malfunction code