Intel® Server System M70KLP Family Service Guide
74
Caution:
Processor heat sinks are easily damaged if handled improperly. See the following image for proper
handling.
Figure 94. Processor Heat Sink Handling
5.9.1
Processor Heat Sink Module (PHM) Removal
1.
Identify and locate the faulty processor.
Figure 95. PHM Assembly Removal from Processor Socket
2.
Ensure the heat sink anti-tilt wire located over each of the four heat sink fasteners are in the outward
position (see Letter A).
3.
Fully loosen all four heat sink fasteners in the following order
–
4, 3, 2, 1 (see Letter B).
•
Reference the label atop of the heat sink for fastener numbering
4.
Set all four anti-tilt wires on the heat sink to the inward position (see Letter C).
5.
Carefully grasp the PHM and lift it straight up and off the server board (see Letter D).
6.
With the processor facing up, set the PHM down onto a flat surface.
7.
Visually inspect that the processor socket is free of damage or contamination.
Note:
If debris is observed, blow it away gently. Do not use tweezers or any other hard tools to
remove the debris.
Содержание M70KLP Series
Страница 2: ...Intel Server System M70KLP Family Service Guide Blank page...
Страница 94: ...Intel Server System M70KLP Family Service Guide 92 1 2 3 4 5 6 1 2 3...
Страница 95: ...Intel Server System M70KLP Family Service Guide 93 1 2 3 4 5...
Страница 96: ...Intel Server System M70KLP Family Service Guide 94 7 8 9 10 11 12 4 5 6...
Страница 97: ...Intel Server System M70KLP Family Service Guide 95 6 7 8 9 10...
Страница 106: ...Intel Server System M70KLP Family Service Guide 104 1 2 3 4 5 ESD 6 1 2 3...
Страница 107: ...Intel Server System M70KLP Family Service Guide 105 1 2 3 4 5...