Intel® Server System M70KLP Family Service Guide
40
Figure 44. Riser Card - Auxiliary PCIe* Cable Connection
5.
(If present) Reattach all auxiliary PCIe cables to the backside of the riser card. Cables should be locked
when fully seated.
Figure 45. Riser Card Installation into System
6.
Align the back of the riser assembly to the slot guides on the chassis back panel (see Letter A).
7.
Carefully lower the riser assembly into the chassis, ensuring the edge connector of the riser card
aligns with the riser slot on the server board.
8.
Insert the riser card into the slot using even downward pressure until the assembly is fully seated.
9.
Push down on the blue tab on the end of the rise assembly and turn it clockwise until the riser
assembly is locked in place with the server board (see Letter B).
10.
Fold down the blue tab.